BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z143008
Premises: 3612 BROADWAY MANHATTAN BIN: 1062060     Block: 2080   Lot: 59
   
Application Completed and Certified

Filed: 3612 BROADWAY Census Tract:   233 Health Area:  0620
BASEMENT AND FIRST FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10031 Community Board:   109
DOB Cross Street(s):   WEST 148 STREET,    WEST 149 STREET
Status:   C - JOB IS SIGNED OFF 07/29/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/10/2014 7:51 AM
Application Entered:   02/10/2014 Job Start Date:   02/11/2014
Last Change:   07/29/2014 Job End Date:   07/01/2014
Appointment Status:   
Last Inspection By:   URIM SYLA       On     07/25/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011464 Licensee Name: THOMAS E JOCELYN III
Firm: 001324 Firm Name: SCIENTIFIC ELEC. CO. INC
Firm Phone: 718-320-2023  Firm Address: 1475 EAST 222ND STREET BRONX NY 10469 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $117.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121810120
Building Used As:   K - Store
Store / Other:   RESTAURANT/BAR
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JASON JANAWSKY
Owner Business Name: SOUTH LAKE HOS. INC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10  12    10  20         
001    14  16    14  15         
Buildings Total 24  28    24     35           
Total Units : 120 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/23/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  BRANCH WIRING FOR LIGHTS AND POWER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z143008
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/17/2014 07/23/2014 UMS A (50) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 07/25/2014 07/29/2014 UMS C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z143008
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1ST FLOOR MULTIPLE CONDUCTORS IN ONE GROUND LUG IN FIRST FLOOR SUBPANEL 110.14A
RSLV 07/17/2014 07/17/2014 07/25/2014
 
002 (999) OTHER
1ST FLOOR NO SIMUTANEOUS DISCONNECTING MEANS USED FOR MULTIWIREBRANCH CIRCUITS IN FIRST FLOOR SUB PANEL 210.4B
RSLV 07/17/2014 07/17/2014 07/25/2014
 
003 (999) OTHER
OUTDOOR CUMINAIRE BOXES MISSING COVERS 314.28C
RSLV 07/17/2014 07/17/2014 07/25/2014
 
004 (999) OTHER
OUTDOOR GFCI RECEPTACLE OUTLETS NOT WR TYPE 406.8B1
RSLV 07/17/2014 07/17/2014 07/25/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.