BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z143007
Premises: 3631 BROADWAY MANHATTAN BIN: 1062444     Block: 2096   Lot: 34
   
Application Completed and Certified

Filed: 600 W 150 ST Census Tract:   233 Health Area:  0620
BASEMENT/1ST FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10031 Community Board:   109
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 03/20/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/09/2014 6:34 PM
Application Entered:   02/09/2014 Job Start Date:   02/10/2014
Last Change:   03/20/2015 Job End Date:   08/20/2014
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     08/19/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010910 Licensee Name: DAVID HARARI
Firm: 002193 Firm Name: VEGA ELECTRIC CORP.
Firm Phone: 347-386-1908  Firm Address: 2886 NOSTRAND AVENUE BROOKLYN NY 11229 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $316.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (6  Stores, 40 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RAFAEL LOPAZ
Owner Business Name: 600 WEST 150ST LLC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  #3 WIRE
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  #3/0 WIRE
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  5  100 AMPS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  20  30  20  20             
001  20  30  20  20             
001  20  30  20  20             
001  20  30  20  20             
001  20  30  20  20             
Buildings Total 100  150  25  100  100                
Total Units : 475 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 5 - Removed Meters 1 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/09/2014 Notice: 1 - FIRST NOTICE 07/23/2014
Power Issued: 02/09/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REQUEST TO INSTALL FIVE METERS SINGLE PHASE 100 AMPS. GENERAL REWIRING, OUTLETS, SWITCHES, LIGHTS IN FIRST FLOOR.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z143007
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/30/2014 06/10/2014 GYM Z (0) (0) Y
INSPECTION COMMENTS: CANCEL
 
(2) 07/10/2014 07/23/2014 UMS A E (90) (7) Y
INSPECTION COMMENTS: VIOL
 
(3) 08/19/2014 08/25/2014 BMP C R E (50) (0) Y
INSPECTION COMMENTS: SEE FILING DETAILS

OBJECTION FOR APPLICATION #: Z143007
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT/FEEDER CONCUCTORS NOT SUPPORTED PROPERLY 320.30
RSLV 07/10/2014 07/10/2014 08/19/2014
 
002 (999) OTHER
BSMT/NEUTRAL BONDED TO EGC BEYOND SERVICE DISCONNECT 250.24A5
RSLV 07/10/2014 07/10/2014 08/19/2014
 
003 (999) OTHER
BSMT/MAIN SERVICE DISCONNECT MISSING GEC TO WATER MAIN 250.24D
RSLV 07/10/2014 07/10/2014 08/19/2014
 
004 (999) OTHER
BSMT/MAIN SERVICE DISCONNECT MISSING SUPPLEMENTAL GEC 250.53D2
RSLV 07/10/2014 07/10/2014 08/19/2014
 
005 (999) OTHER
BSMT/NO FIRE STOPING USED IN BSMT 300.21
RSLV 07/10/2014 07/10/2014 08/19/2014
 
006 (999) OTHER
NO BUSSING / ALL FEEDERS 300
RSLV 07/10/2014 07/10/2014 08/19/2014
 
007 (999) OTHER
ALL APTS/ RECEPTACALE OUTLETS IN ALL APRTS 210.52
RSLV 07/10/2014 07/10/2014 08/19/2014