BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z142921
Premises: 101 WEST 80 STREET MANHATTAN BIN: 1031975     Block: 1211   Lot: 29
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 101 W 80 ST Census Tract:   165 Health Area:  3500
GROUND FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/02/2014 12:36 PM
Application Entered:   02/02/2014 Job Start Date:   02/02/2014
Last Change:   08/22/2025 Job End Date:   01/31/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     08/27/2015      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011252 Licensee Name: ALBERT V DATTOLO
Firm: 001211 Firm Name: RAINBOW ELECTRIC CO., INC
Firm Phone: 718-521-0926  Firm Address: 76-18 ROCKAWAY BLVD WOODHAVEN NY 11421 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $125.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES JENNINGS
Owner Business Name: JA JENNINGS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS      10             
GND  22  25    10  70             
Buildings Total 30  25    15  80                
Total Units : 150 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/02/2015
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALL LIGHT FIXTURES GROUND AND BASEMENT FLOORS.USED EXISTING POWER AND WIRING .CHANGED PANEL ON GROUND FLOOR USED OLD WIRING.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z142921
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/14/2015 07/21/2015 UMS J (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT FAMILIAR WITH JOB. CONTRACTOR NOT ABLE TO LOCATE PANEL
 
(2) 07/28/2015 08/05/2015 LUF P (25) (0) Y
INSPECTION COMMENTS: CONTR. COULDNT ACCESS WORK TO BE INSPECTED
 
(3) 08/19/2015 08/25/2015 CBK N (30) (0) Y
INSPECTION COMMENTS: WAITED AND CALLED BUT NO ONE SHOWED UP
 
(4) 08/27/2015 09/02/2015 NRS V (60) (13) Y
INSPECTION COMMENTS: 420 COLUMBUS AVE.*RITUALS* CONTRACTOR NOT FAMILIAR WITH JOB

OBJECTION FOR APPLICATION #: Z142921
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
GR: NO SHOW WIN.RECE ON NORTH SIDE.. 210.62
OPEN 08/27/2015 08/27/2015
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
GR: SALES FLOOR SINK.RECE UNDERNEATH
OPEN 08/27/2015 08/27/2015
 
003 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
BASE: PANEL E.B.J.TERMINATED ON NEUTRAL
OPEN 08/27/2015 08/27/2015
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BASE: PANEL 2ND E.M.T.FROM LEFT ON TOP LOCKNUT
OPEN 08/27/2015 08/27/2015
 
005 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
BASE: PANEL DISCONNECT E.B.J.ON NEUTRAL
OPEN 08/27/2015 08/27/2015
 
006 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
BASE: TOP OF PANEL 3/4" CONDUIT
OPEN 08/27/2015 08/27/2015
 
007 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BASE
OPEN 08/27/2015 08/27/2015
 
008 ( 30) OUTLET BOXES ARE NOT SECURED
BASE: 1900 BOX SUPPORTED LIGHT FIXTURES
OPEN 08/27/2015 08/27/2015
 
009 (999) OTHER
BASE: BX NOT SUPPORTED IN BASE & GR.FL.. 320.30
OPEN 08/27/2015 08/27/2015
 
010 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
GR: CONFERENCE TABLE FLOOR RECE ASEMBLY
OPEN 08/27/2015 08/27/2015
 
011 (252) LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE
GR: CONFERENCE TABLE RECE
OPEN 08/27/2015 08/27/2015
 
012 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
GR
OPEN 08/27/2015 08/27/2015
 
013 (999) OTHER
GR: TV FLEX CORD GOES INTO DROP CEILING.. 400.8
OPEN 08/27/2015 08/27/2015