| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER GR: NO SHOW WIN.RECE ON NORTH SIDE.. 210.62 |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 002 |
( 53) |
GFCI HAS NOT BEEN PROVIDED GR: SALES FLOOR SINK.RECE UNDERNEATH |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 003 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH BASE: PANEL E.B.J.TERMINATED ON NEUTRAL |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BASE: PANEL 2ND E.M.T.FROM LEFT ON TOP LOCKNUT |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 005 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH BASE: PANEL DISCONNECT E.B.J.ON NEUTRAL |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 006 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED BASE: TOP OF PANEL 3/4" CONDUIT |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 007 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BASE |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 008 |
( 30) |
OUTLET BOXES ARE NOT SECURED BASE: 1900 BOX SUPPORTED LIGHT FIXTURES |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 009 |
(999) |
OTHER BASE: BX NOT SUPPORTED IN BASE & GR.FL.. 320.30 |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 010 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED GR: CONFERENCE TABLE FLOOR RECE ASEMBLY |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 011 |
(252) |
LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE GR: CONFERENCE TABLE RECE |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 012 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY GR |
OPEN |
08/27/2015 |
08/27/2015 |
|
| |
| 013 |
(999) |
OTHER GR: TV FLEX CORD GOES INTO DROP CEILING.. 400.8 |
OPEN |
08/27/2015 |
08/27/2015 |
|