BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
Building Overview Work Items |
QUANTITY |
DESCRIPTION |
SERVICE SWITCHES |
|
A. Up to 100 AMPS |
2 |
60 AMPERES |
B. 101 Up to 200 AMPS |
1 |
200 AMPERE |
C. 201 Up to 600 AMPS |
0 |
|
D. 601 Up to 1200 AMPS |
0 |
|
E. Over 1200 AMPS |
0 |
|
SER. ENT. & FDR COND (EACH SET) |
|
A. Up to #2 CONDUCTOR |
2 |
#2 THHN |
B. Over #2 to 1/0 |
0 |
|
C. Over 1/0 to 250 MCM |
1 |
3/0 THHN |
D. Over 250 MCM |
0 |
|
PANELS |
|
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
2 |
20 CKTS |
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
30 CKTS |
C. 3 Phase Up to 225 AMPS |
0 |
|
D. 3 Phase Over 225 AMPS |
0 |
|
ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
B. Each Additional 10 Floors Or Less |
0 |
|
BOILER CONTROLS |
0 |
|
OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
|
001 |
(999) |
OTHER BSMT: 200 AMP COMB PANEL.2 100 AMP SERVICE SW NEUTRAL BAR NOT BONDAS PER ART.250.28 |
OPEN |
06/12/2014 |
11/19/2014 |
|
|
002 |
( 30) |
OUTLET BOXES ARE NOT SECURED BSMT: COMB PANEL NEUTRAL BAR |
OPEN |
06/12/2014 |
11/19/2014 |
|
|
003 |
(999) |
OTHER A) BSMT: 200 AMP COMB PANEL MAIN BREAKER IS NOT PER ART.408.36 |
OPEN |
06/12/2014 |
11/19/2014 |
|
|
004 |
(999) |
OTHER B) BSMT: GROUNDING ELECTRODE CONDUCTOR IS NOT AS PER ART.250.52 |
OPEN |
06/12/2014 |
11/19/2014 |
|
|
005 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX BSMT: KO MISSING |
OPEN |
06/12/2014 |
11/19/2014 |
|
|
006 |
(999) |
OTHER C) BSMT: COPPER BUS BAR NOT LISTED. 110.2(GROUNDING) |
OPEN |
06/12/2014 |
11/19/2014 |
|
|
007 |
(999) |
OTHER D) BSMT: COMB PANEL SUITABLE FOR US AS SERVICE MAIN BREAKER IS IN-STALLED. 110.2 |
OPEN |
06/12/2014 |
11/19/2014 |
|