Electrical Application Details for App #: Z142294
Premises: 539 WEST 142 STREET MANHATTAN BIN: 1061846     Block: 2074   Lot: 9
  Printable (PDF) version of this Permit  

Filed: 539 W 142 ST Census Tract:   229 Health Area:  0620
CELLAR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10031 Community Board:   109
Related Job Number:    104922489
DOB Cross Street(s):   HAMILTON PLACE,    BROADWAY
Status:   P - OBJECTN PENDING AT CONTRACTOR 11/25/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/04/2013 8:44 AM
Application Entered:   12/04/2013 Job Start Date:   12/04/2013
Last Change:   11/25/2014 Job End Date:   06/04/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DIMAGGIO, PHILLIP       On     11/19/2014      
Field Disp:   H - NO PROGRESS ON JOB
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  X - NOT REMOVED

License #: 010346 Licensee Name: PHILIP A ROBINSON
Firm: 001157 Firm Name: PHILIP A. ROBINSON
Firm Phone: 718-783-6542  Firm Address: 43-49 10TH STREET.SUITE 107 LONG ISLAND CITY NY 11101-6999 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $228.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WALTER BIGGS
Owner Business Name: RESIDENCE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  60 AMPERES
B. 101 Up to 200 AMPS  1  200 AMPERE
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  #2 THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 THHN
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  20 CKTS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  30 CKTS
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL  CEL               
Buildings Total                 
Total Units : 11 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 6 + New Meters 0 - Removed Meters 3 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 12/04/2013 Notice: C - CALL TO OFFICE 11/25/2014
Power Issued: 12/04/2013 Response:  

Follow-Up:
Contractor's Comments:  REDUCING THE NUMBERS OF METERS IN BUILDING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z142294
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/12/2014 06/19/2014 GYM A E (60) (7) Y
INSPECTION COMMENTS: NONE
 
(2) 11/19/2014 11/25/2014 PDI H X E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z142294
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: 200 AMP COMB PANEL.2 100 AMP SERVICE SW NEUTRAL BAR NOT BONDAS PER ART.250.28
OPEN 06/12/2014 11/19/2014
 
002 ( 30) OUTLET BOXES ARE NOT SECURED
BSMT: COMB PANEL NEUTRAL BAR
OPEN 06/12/2014 11/19/2014
 
003 (999) OTHER
A) BSMT: 200 AMP COMB PANEL MAIN BREAKER IS NOT PER ART.408.36
OPEN 06/12/2014 11/19/2014
 
004 (999) OTHER
B) BSMT: GROUNDING ELECTRODE CONDUCTOR IS NOT AS PER ART.250.52
OPEN 06/12/2014 11/19/2014
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BSMT: KO MISSING
OPEN 06/12/2014 11/19/2014
 
006 (999) OTHER
C) BSMT: COPPER BUS BAR NOT LISTED. 110.2(GROUNDING)
OPEN 06/12/2014 11/19/2014
 
007 (999) OTHER
D) BSMT: COMB PANEL SUITABLE FOR US AS SERVICE MAIN BREAKER IS IN-STALLED. 110.2
OPEN 06/12/2014 11/19/2014