| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(125) |
PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE (BASEMENT) 90A ELEV. OCPD IN BOILER ROOM PANEL |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 002 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (BASEMENT) MOTOR ROOM. 1P13312. IN PANEL 250.8 |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT) MOTOR ROOM. 1P13312. IN ELEV. DISCONNECT |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 004 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT) IN BOILER ROOM PANEL, FEEDING ELEVATORS: MECH GROUND DEFECTIVE,E.G.C. NOT SIZED AS PER 250.122 |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 005 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (BASEMENT) MOTOR ROOM. 1P13312. PANEL, TROUGH |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 006 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (BASEMENT) MOTOR ROOM. 1P13312 |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 007 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (BASEMENT) MOTOR ROOM. 1P13312. MOTOR ROOM & OUTSIDE OF MOTOR ROOMS. |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 008 |
(999) |
OTHER (BASEMENT) MOTOR ROOM. 1P13312. MOROR NOT FUSED AS PER 430.52 |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 009 |
(999) |
OTHER (BASEMENT) MOTOR ROOM. 1P13312. #6AWG TAP FEEDING PANEL NOT AS PER 240.21 |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 010 |
(999) |
OTHER (BASEMENT) MOTOR ROOM. 1P13312. MORE THAN 2 CONDUCTOR UNDER SPLIT BOLTCONNECTOR IN TROUGH 110.3 |
OPEN |
03/23/2016 |
03/23/2016 |
|
| |
| 011 |
(999) |
OTHER (BASEMENT) BOTH MOTOR ROOM. NO ARC FLUSH WARNING 110.16 |
OPEN |
03/23/2016 |
03/23/2016 |
|