| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400A, 3PHASE 120/208 |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
25 |
3 #6THHN BX |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
2 |
4-500MCM THHN |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
24 |
20CKTS, 120/208, 125A |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
200A, 42CKT, 120/208, 3PH |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(133) |
NO GROUND ROD: BASEMENT OR OUTSIDE BSMT: WATER PIPE NOT SUPPLEMENTED BY GROUND ROD PER 250.53D2 |
RSLV |
11/04/2013 |
12/02/2013 |
12/05/2014 |
| |
| 002 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH BSMT: NEUTRAL BONDED IN PLP METER PAN. 250.24A5 |
RSLV |
11/04/2013 |
12/02/2013 |
12/05/2014 |
| |
| 003 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BSMT: APT.RISER CABLES NOT PROPERLY SUPPORTED TO BSMT CEILING.320.30 |
RSLV |
11/04/2013 |
12/02/2013 |
12/05/2014 |
| |
| 004 |
(282) |
MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS 3FL: APT.33 ONLY 1 SML APPL.CKT/G.F.C.I.RECEPTACLE PROVIDED FOR KIT-CHEN. 210.52B1 |
RSLV |
11/04/2013 |
12/02/2013 |
12/05/2014 |
| |
| 005 |
(138) |
METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY 4FL: APT.37 BX/EMT CHANGEOVER MISSING CONNECTORS/LOCKNUTS(KITCHENRECEPTACLES. 300.10 |
RSLV |
11/04/2013 |
12/02/2013 |
12/05/2014 |
| |
| 006 |
(999) |
OTHER BASEMENT NEUTRAL GROUNDED BEYOND LOAD SICK OF SERVICE SWITCH. PLPPOND ART 250.24 A5 |
RSLV |
12/05/2014 |
12/05/2014 |
12/26/2014 |
| |
| 007 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BASEMENT ARDEMED CABLES NOT PROPERLY SUPPORTED |
RSLV |
12/05/2014 |
12/05/2014 |
12/26/2014 |