NYC Department of Buildings
Electrical Application Details for App #: Z141442
Premises: 8 WEST 108 STREET MANHATTAN BIN: 1055696     Block: 1843   Lot: 40
   
Application Completed and Certified

Filed: 8 W 108 ST Census Tract:   193 Health Area:  2320
PARTIAL REWIRE OF ENTIRE SERVI Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK WEST,    MANHATTAN AVENUE
Status:   C - JOB IS SIGNED OFF 01/10/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/01/2013 9:23 AM
Application Entered:   10/01/2013 Job Start Date:   10/01/2013
Last Change:   01/10/2015 Job End Date:   09/20/2014
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     12/26/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012008 Licensee Name: JAROSLAW K KURACH
Firm: 003679 Firm Name: BELMONT ELECTRICAL, INC
Firm Phone: 646-484-6641  Firm Address: 42 WEST 38TH STREET, STE 503 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,089.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HARRY TAWIL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400A, 3PHASE 120/208
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  25  3 #6THHN BX
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  4-500MCM THHN
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  24  20CKTS, 120/208, 125A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200A, 42CKT, 120/208, 3PH
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001                       
002                       
003                       
004                       
005                       
006                       
Buildings Total   48                      
Total Units : 48 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 24 #4-Wire 1 #10-Wire 0
Existing Meters 25 + New Meters 25 - Removed Meters 25 = Total Meters 25

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/01/2013 Notice: 1 - FIRST NOTICE 12/11/2014
Power Issued: 10/01/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SERVICE REPLACE, PANEL AND GFI'S IN THE KITCHEN IN EACH APT.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z141442
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/04/2013 11/14/2013 LBI V G (90) (5) Y
INSPECTION COMMENTS: SVC WORK IMCOMPLETE/TEMPED OUT.INSPECTED AOTS.25,28,32,33,37,38,41
 
(2) 12/02/2013 12/10/2013 PHG H X E (25) (0) Y
INSPECTION COMMENTS: SERVICE WORK TEMPED OUT NOT READY FOR INSPECTION
 
(3) 12/05/2014 12/11/2014 PDI V R E (50) (2) Y
INSPECTION COMMENTS: ONLY ONEC1) OBJECTION HAS BEEN RESOLVED. THIS JOB NEEDS ATTENTION WORK MONTH ALL AROUND IS VERY POOR. COULD NOT GET ACCESS IN TO MANY APT TO CHECK. NOT ENOUGH TIME
 
(4) 12/26/2014 01/06/2015 GYM C R E (95) (0) Y
INSPECTION COMMENTS: INSPECTED #29,#36,#37 APTS ONLY

OBJECTION FOR APPLICATION #: Z141442
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (133) NO GROUND ROD: BASEMENT OR OUTSIDE
BSMT: WATER PIPE NOT SUPPLEMENTED BY GROUND ROD PER 250.53D2
RSLV 11/04/2013 12/02/2013 12/05/2014
 
002 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
BSMT: NEUTRAL BONDED IN PLP METER PAN. 250.24A5
RSLV 11/04/2013 12/02/2013 12/05/2014
 
003 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BSMT: APT.RISER CABLES NOT PROPERLY SUPPORTED TO BSMT CEILING.320.30
RSLV 11/04/2013 12/02/2013 12/05/2014
 
004 (282) MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS
3FL: APT.33 ONLY 1 SML APPL.CKT/G.F.C.I.RECEPTACLE PROVIDED FOR KIT-CHEN. 210.52B1
RSLV 11/04/2013 12/02/2013 12/05/2014
 
005 (138) METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY
4FL: APT.37 BX/EMT CHANGEOVER MISSING CONNECTORS/LOCKNUTS(KITCHENRECEPTACLES. 300.10
RSLV 11/04/2013 12/02/2013 12/05/2014
 
006 (999) OTHER
BASEMENT NEUTRAL GROUNDED BEYOND LOAD SICK OF SERVICE SWITCH. PLPPOND ART 250.24 A5
RSLV 12/05/2014 12/05/2014 12/26/2014
 
007 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BASEMENT ARDEMED CABLES NOT PROPERLY SUPPORTED
RSLV 12/05/2014 12/05/2014 12/26/2014