BIS Menu  |  Electrical Applications  |  Comments  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z141190
Premises: 233 WEST 139 STREET MANHATTAN BIN: 1060360     Block: 2025   Lot: 16
   
Application Completed and Certified

Filed: 233 W 139 ST Census Tract:   230 Health Area:  1000
CELLAR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10030 Community Board:   110
DOB Cross Street(s):   ADAM CLAYTON POWELL JR BOULEVARD,    PEDESTRIAN PATH
Status:   C - JOB IS SIGNED OFF 09/29/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/09/2013 9:14 AM
Application Entered:   09/09/2013 Job Start Date:   09/09/2013
Last Change:   09/29/2014 Job End Date:   12/31/2013
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     09/23/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011355 Licensee Name: CARMINE L LIPPOLIS
Firm: 002775 Firm Name: LIPPOLIS ELECTRIC, INC.
Firm Phone: 718-892-4055  Firm Address: 4459 BRONX BOULEVARD BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $122.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JANE/RODERICK MYERS/FOUQUET
Authorized Representative:  RICHARD SANSONE
Relationship To Owner:   GC-TRI-COUNTY BUILDING


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1-200A
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  1-100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  1-200A
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 3 + New Meters 1 - Removed Meters 1 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/09/2013 Notice: 1 - FIRST NOTICE 09/19/2014
Power Issued: 09/09/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ELECTRICAL SERVICE UPGRADE ONLY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z141190
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/19/2014 08/25/2014 UMS A D (35) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 09/16/2014 09/19/2014 GYM A R E (55) (2) Y
INSPECTION COMMENTS: (1)NEW 3W METER PANEL (1) 200 AMP COMB PANEL (1) SET 3/0 AWG
 
(3) 09/23/2014 09/29/2014 BMP C R E (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z141190
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT 6 AWG BLACK WIRE USED AS SUPPLY SIDE BONDING JUMPER TAPPEDGREEN 250.119(A)
RSLV 08/19/2014 08/19/2014 09/16/2014
 
002 (999) OTHER
BASEMENT NO BUSHING PROVIDED FOR UAWG FEEDER AT BOTH ENDS 300.4(G)
RSLV 08/19/2014 08/19/2014 09/16/2014
 
003 (999) OTHER
BASEMENT WHITE CONDUCTOR COMING FROM A CABLE ASSEMBLY NOT IDENTIFIEDAS UNGROUNDED CONDUCTOR AT BOTH ENDS 200.7(C)
RSLV 08/19/2014 08/19/2014 09/16/2014
 
004 (999) OTHER
BASEMENT SERVICE ENT. CONCENTRIC KNOCK OUTS NOT BONDED AS PER ART250.92
RSLV 09/16/2014 09/16/2014 09/23/2014
 
005 ( 30) OUTLET BOXES ARE NOT SECURED
BASEMENT KO MISSING ENISON BOX
RSLV 09/16/2014 09/16/2014 09/23/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.