BIS Menu  |  Elevators  |  Property Profile  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z140947
Premises: 622 9 AVENUE MANHATTAN BIN: 1024982     Block: 1035   Lot: 1
   
Application Completed and Certified

Filed: 630 9 AV Census Tract:   121 Health Area:  4500
10TH FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   G
NEW YORK, NY 10036 Community Board:   104
DOB Cross Street(s):   WEST 44 STREET,    WEST 45 STREET
Status:   C - JOB IS SIGNED OFF 03/04/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/21/2013 5:52 PM
Application Entered:   08/21/2013 Job Start Date:   08/21/2013
Last Change:   03/04/2014 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     02/19/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $266.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ELECTRONIC THEATRE CONTROLS INC
Owner Business Name: PROPERTY MANAGER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
010      122    166  22     
Buildings Total   122    166     22         
Total Units : 314 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/08/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z140947
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/30/2013 01/08/2014 TSO V (85) (10) Y
INSPECTION COMMENTS: N/A TO FEEDES BASEMENT AC
 
(2) 02/19/2014 03/04/2014 EDB C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z140947
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
DINNER ROOM CONDUCTER IN TROUGH. NOT DECATED 730 376.22
RSLV 12/30/2013 12/30/2013 02/19/2014
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
MECHICAIL ROOM KO'S PANEL AND AC DISCONNECT
RSLV 12/30/2013 12/30/2013 02/19/2014
 
003 (999) OTHER
OCP A C - 2 TOO LARGE 110.3
RSLV 12/30/2013 12/30/2013 02/19/2014
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
HALL PULL BOX CEILLING A C- 2 NO COVER
RSLV 12/30/2013 12/30/2013 02/19/2014
 
005 ( 42) BUSHINGS ARE MISSING OR LOOSE
HALL PULL BOX CEILING A C - 2 BUSHING
RSLV 12/30/2013 12/30/2013 02/19/2014
 
006 (999) OTHER
HALL PULL BOX CEILING A C - 2 FMC NO GROUND 250.118
RSLV 12/30/2013 12/30/2013 02/19/2014
 
007 ( 42) BUSHINGS ARE MISSING OR LOOSE
HALL NO BUSHING IN 3/0 MC CABLE PULLBOX
RSLV 12/30/2013 12/30/2013 02/19/2014
 
008 (999) OTHER
OUTSIDE OCP AC COMPRESSOR OUTSIDE TOO LARGE 110.3
RSLV 12/30/2013 12/30/2013 02/19/2014
 
009 (999) OTHER
OUTSIDE 2 COND UNDER 1 LUG AC COMPRESSOR 110.3
RSLV 12/30/2013 12/30/2013 02/19/2014
 
010 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
OFFICES KO'S TRACKS OFFICES
RSLV 12/30/2013 12/30/2013 02/19/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Property Profile  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back