BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z140506
Premises: 240 RIVERSIDE BOULEVARD MANHATTAN BIN: 1087072     Block: 1171   Lot: 7503
   
Application Completed and Certified

Filed: 240 RIVERSIDE BLVD Census Tract:   159 Health Area:  3900
APT #27A Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10069 Community Board:   107
DOB Cross Street(s):   WEST 71 STREET,    WEST 72 STREET
Status:   C - JOB IS SIGNED OFF 05/22/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/24/2013 6:58 PM
Application Entered:   07/24/2013 Job Start Date:   07/25/2013
Last Change:   05/22/2014 Job End Date:   07/25/2014
Appointment Status:   
Last Inspection By:   DIMAGGIO, PHILLIP       On     05/13/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011819 Licensee Name: ROBERT A LOGOZIO
Firm: 003506 Firm Name: TEAM ELECTRIC, INC
Firm Phone: 212-685-8585  Firm Address: 20 WEST 36TH STREET, 10TH FL NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $45.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NEDELMAN MR
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
027  27A  11    11             
Buildings Total 11    11                
Total Units : 30 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/25/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z140506
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/13/2014 03/25/2014 NRS A (35) (6) Y
INSPECTION COMMENTS: NONE
 
(2) 04/14/2014 04/30/2014 BMP N (20) (0) Y
INSPECTION COMMENTS: SPOKE W/CONTRACTOR. OCCUPANT CANCELED
 
(3) 04/14/2014 04/30/2014 BMP Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 05/13/2014 05/22/2014 PDI C R (50) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Z140506
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
27 A: BOXES SET TOO DEEP IN WALL: BATH & ADJACENT CLOSET 314.20
RSLV 03/13/2014 03/13/2014 05/13/2014
 
002 (999) OTHER
27 A: ZIP SCRE USED AS GROUND SCREW IN BOXES 250.118 (G) (A)
RSLV 03/13/2014 03/13/2014 05/13/2014
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
27 A: 5" & 4 GANG BOX IN CLOSET OUTSIDE OF BATHRM
RSLV 03/13/2014 03/13/2014 05/13/2014
 
004 (999) OTHER
27 A: 4 GANG BOX HAS MC WITH ROMEX CONNECTOR 110.2
RSLV 03/13/2014 03/13/2014 05/13/2014
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
27 A: 5" BOX HAS NO COVER PLATE IN CLOSET
RSLV 03/13/2014 03/13/2014 05/13/2014
 
006 ( 19) DEFECTIVE WIRING IS IN USE
27 A: 5" GROUND WIRES OF AC CAB NOT SPLICED TOGETHER
RSLV 03/13/2014 03/13/2014 05/13/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order