BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z140376
Premises: 845 WEST END AVENUE MANHATTAN BIN: 1057155     Block: 1889   Lot: 7502
   
Application Completed and Certified

Filed: 845 W END AV Census Tract:   187 Health Area:  3110
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   WEST 101 STREET,    WEST 102 STREET
Status:   C - JOB IS SIGNED OFF 11/23/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/16/2013 7:23 AM
Application Entered:   07/16/2013 Job Start Date:   07/16/2013
Last Change:   11/23/2013 Job End Date:   07/17/2013
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     11/19/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011056 Licensee Name: BARRY SAXE
Firm: 002286 Firm Name: CEDAR ELEC'L CONT'RS INC.
Firm Phone: 212-594-2802  Firm Address: 369 WEST 34TH STREET 2ND FLR NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LOU BLUM
Owner Business Name: ATLAS CAPITAL
Authorized Representative:  LOU BLUM
Relationship To Owner:   VP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 38 #4-Wire 0 #10-Wire 0
Existing Meters 91 + New Meters 38 - Removed Meters 38 = Total Meters 91

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/16/2013 Notice: 1 - FIRST NOTICE 09/25/2013
Power Issued: 07/16/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS APPLICATION IS TO COVER WORK APPROVED BY THE ADVISORY BOARD CALENDER NUMBER #49544 WILL BRING DRAWING TO INSPECTION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z140376
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/14/2013 09/25/2013 GYM A E (45) (9) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 11/19/2013 11/23/2013 BMP C R E (80) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z140376
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: SERVICE SW #5 600 AMP.1 #500 MCM CU PER PHASE AND NEUTRAL IN -1 - 3 1/2" NIPPLE IS NOT AS PER DRAWING.. - 110.2 CAL #47544 REV O
RSLV 09/14/2013 09/14/2013 11/19/2013
 
002 (999) OTHER
A) BSMT: NEW 600 AMP SER SW #5 NOT SHOW ON DRAWING... - 110.2
RSLV 09/14/2013 09/14/2013 11/19/2013
 
003 (999) OTHER
B) BSMT: ELECTRICAL SERVICE ROOM LAYOUT DOORS IS NOT AS PER DRAWING- 110.2. CAL #47544 REV O
RSLV 09/14/2013 09/14/2013 11/19/2013
 
004 (999) OTHER
C) BSMT: NEW 600 AMP SER SW #5 NOT GROUPED... - 225.34A 230.72
RSLV 09/14/2013 09/14/2013 11/19/2013
 
005 (999) OTHER
D) 8FL: VERTICAL RACEWAY SUPPORT SPACING IS NOT AS PER TABLE 300.19(8FL ALL FEEDERS)
RSLV 09/14/2013 09/14/2013 11/19/2013
 
006 (999) OTHER
E) BSMT: 600 AMP SERVICE SW NEUTRAL BAR NOT BONDED... - 250.28
RSLV 09/14/2013 09/14/2013 11/19/2013
 
007 (999) OTHER
F) BSMT: 600 AMP SERVICE PHASE AND NEUTRAL NOT GROUPED.. - 300.20
RSLV 09/14/2013 09/14/2013 11/19/2013
 
008 (999) OTHER
G) BSMT: NEC ART 250.92 SERVICE ENTRANCE RACEWAY NOT BONDED(CONDUIT)
RSLV 09/14/2013 09/14/2013 11/19/2013
 
009 (999) OTHER
H) BSMT: NO PANIC HARDWARE NOT PROVIDED DOORS... - ART.110.26
RSLV 09/14/2013 09/14/2013 11/19/2013