| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: SERVICE SW #5 600 AMP.1 #500 MCM CU PER PHASE AND NEUTRAL IN -1 - 3 1/2" NIPPLE IS NOT AS PER DRAWING.. - 110.2 CAL #47544 REV O |
RSLV |
09/14/2013 |
09/14/2013 |
11/19/2013 |
| |
| 002 |
(999) |
OTHER A) BSMT: NEW 600 AMP SER SW #5 NOT SHOW ON DRAWING... - 110.2 |
RSLV |
09/14/2013 |
09/14/2013 |
11/19/2013 |
| |
| 003 |
(999) |
OTHER B) BSMT: ELECTRICAL SERVICE ROOM LAYOUT DOORS IS NOT AS PER DRAWING- 110.2. CAL #47544 REV O |
RSLV |
09/14/2013 |
09/14/2013 |
11/19/2013 |
| |
| 004 |
(999) |
OTHER C) BSMT: NEW 600 AMP SER SW #5 NOT GROUPED... - 225.34A 230.72 |
RSLV |
09/14/2013 |
09/14/2013 |
11/19/2013 |
| |
| 005 |
(999) |
OTHER D) 8FL: VERTICAL RACEWAY SUPPORT SPACING IS NOT AS PER TABLE 300.19(8FL ALL FEEDERS) |
RSLV |
09/14/2013 |
09/14/2013 |
11/19/2013 |
| |
| 006 |
(999) |
OTHER E) BSMT: 600 AMP SERVICE SW NEUTRAL BAR NOT BONDED... - 250.28 |
RSLV |
09/14/2013 |
09/14/2013 |
11/19/2013 |
| |
| 007 |
(999) |
OTHER F) BSMT: 600 AMP SERVICE PHASE AND NEUTRAL NOT GROUPED.. - 300.20 |
RSLV |
09/14/2013 |
09/14/2013 |
11/19/2013 |
| |
| 008 |
(999) |
OTHER G) BSMT: NEC ART 250.92 SERVICE ENTRANCE RACEWAY NOT BONDED(CONDUIT) |
RSLV |
09/14/2013 |
09/14/2013 |
11/19/2013 |
| |
| 009 |
(999) |
OTHER H) BSMT: NO PANIC HARDWARE NOT PROVIDED DOORS... - ART.110.26 |
RSLV |
09/14/2013 |
09/14/2013 |
11/19/2013 |