BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z140334
Premises: 33 WEST END AVENUE MANHATTAN BIN: 1087589     Block: 1171   Lot: 7506
   
Application Completed and Certified

Filed: 33 W END AV Census Tract:   151 Health Area:  3900
REATAIL SPACE C Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   WEST 61 STREET,    WEST 61 DRIVE
Status:   C - JOB IS SIGNED OFF 10/03/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/11/2013 3:26 PM
Application Entered:   07/11/2013 Job Start Date:   07/11/2013
Last Change:   10/03/2013 Job End Date:   07/11/2014
Appointment Status:   
Last Inspection By:   AGELONIAS, ANASTASIOS       On     09/10/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011561 Licensee Name: YEVGENY KOLTUNOV
Firm: 003191 Firm Name: EVERGREEN ELECTRICAL CORP
Firm Phone: 718-768-8936  Firm Address: 4223 1ST AVE, 3RD FL BROOKLYN NY 11232 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $51.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PETER FINE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    14  20  16               
Buildings Total 14  20  16                  
Total Units : 54 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/01/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CLOSING APPLICATION Z133905. IT WAS FILED BY TWO SEPARATE CONTRACTORS AND SHOULD OF BEEN CLOSED AS PART OF Z132889.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z140334
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/25/2013 08/01/2013 JVA V (60) (3) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 09/10/2013 09/16/2013 IOS C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z140334
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
1ST FL: BOXES NOT GROUND THRU-OUT,MC CABLE GRN WIRE NOT TO BOX- 250.118
RSLV 07/25/2013 07/25/2013 09/10/2013
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
1ST FL: SHEET ROCK SCREWS USED TO MOUNT DEVICES.... - 110.2
RSLV 07/25/2013 07/25/2013 09/10/2013
 
003 (999) OTHER
1ST FL: PNL INACCESSIBLE..... - 314.29
RSLV 07/25/2013 07/25/2013 09/10/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.