| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
60AMP. 1- PHASE |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
4 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER 3/0 WIRE GOING TO METER BANK FUSED AT 400AMPS 310.16 |
RSLV |
07/15/2015 |
07/15/2015 |
11/12/2015 |
| |
| 002 |
(999) |
OTHER TWO 3/0 PARALLEL C PHASE CONDUCTORS GOING TO METER BANK DONT COMPLYWITH CONDUCTORS W PARALLEL RULES 310.4 |
RSLV |
07/15/2015 |
07/15/2015 |
11/12/2015 |
| |
| 003 |
(999) |
OTHER WATER METER JUMPER NOT SAME SIZE AS GEC TO WATER PIPE 250.24 |
RSLV |
07/15/2015 |
07/15/2015 |
11/12/2015 |
| |
| 004 |
(999) |
OTHER KITCHEN COUNTERTOP RECEPTACLE OUTLETS DONT MEET SPACE REQUIRMENTS210.52 |
RSLV |
07/15/2015 |
07/15/2015 |
11/12/2015 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS) BATHROOM RECEPTACLES NOT OF TR TYPE 406.11 |
RSLV |
07/15/2015 |
11/12/2015 |
03/02/2016 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS)ALUMINUM CONDUIT USED TO HOUSE CONDUCTORS FOR LANDSCAPING LIGHTS ISIN CONTACT WITH EARTH.. AMEND 300.6 |
RSLV |
11/12/2015 |
11/12/2015 |
03/02/2016 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) OUTDOOR BOX BT OUTDOOR A/C UNIT NOT COVERED.. 314.25 |
RSLV |
11/12/2015 |
11/12/2015 |
03/02/2016 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS)OUTDOOR A/C UNIT NOT FUSED AS PER MANUFACTURE'S SPECS.. 110.3 |
RSLV |
11/12/2015 |
11/12/2015 |
03/02/2016 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS)OUTDOOR A/C DISCONNECT SWITCHES AND A/C UNITS NOT GROUNDED.. 314.4 |
RSLV |
11/12/2015 |
11/12/2015 |
03/02/2016 |