| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED 4A NO GRND FOR FEED LINE CHANGE TO FME 250.112 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 4A NO AFCI PROVIDED FOR BABY ROOM 210.12 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 003 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 4A NO AFCI FOR 120V CKT IN LAUNDRY CLOSET 210.12 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 004 |
( 30) |
OUTLET BOXES ARE NOT SECURED 4A ALL A/C BOXES NOT SUPPORTED 314.23 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 005 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 4A NO AFCI FOR ALL 110V A/C CKTS 210.12 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 006 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED 4A ALL BOXES WITH M/C CABLE NOT BONDED 250.112 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 007 |
(999) |
OTHER 4A LIVING ROOM LIGHT FIXTURE NEEDS APPROVAL 110.2 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 008 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED 4A XFMR LED LIGHTS NOT GRND 250.112 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 009 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 4A BATH ROOM HEATER NOT GFCI PROTECTED 210.8 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 010 |
(999) |
OTHER 4A NO FIRE STOP IN FREIGHT HALL 300.21 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 011 |
(999) |
OTHER 4A BURRIED BOXES IN BED ROOM AND KITCHEN A/C 314.29 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |
| |
| 012 |
( 29) |
OUTLET BOXES ARE NOT COVERED 4A A/C RECEPTICLES NO FINISH PLATE 314.25 |
RSLV |
07/25/2014 |
07/25/2014 |
08/29/2014 |