BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z138327
Premises: 169 WEST 133 STREET MANHATTAN BIN: 1090177     Block: 1918   Lot: 6
   
Application Completed and Certified

Filed: 169 W 133 ST Census Tract:   226 Health Area:  1200
CELLAR, 1THRU6 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10030 Community Board:   110
Related Job Number:    121182326
DOB Cross Street(s):   LENOX AVENUE,    ADAM CLAYTON POWELL JR BOULEVARD
Status:   C - JOB IS SIGNED OFF 11/25/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/11/2013 2:41 PM
Application Entered:   02/11/2013 Job Start Date:   02/12/2013
Last Change:   11/25/2014 Job End Date:   02/13/2014
Appointment Status:   
Last Inspection By:   DIMAGGIO, PHILLIP       On     11/18/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011386 Licensee Name: PETER S CAMPISI
Firm: 001625 Firm Name: SALVATORE CAMPISI & SONS
Firm Phone: 718-497-1383  Firm Address: 18-31 DECATUR STREET ELECTRICAL CONTNG INC RIDGEWOOD NY 11385 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,578.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   HOUSING FOR HOMELESS
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PHIL GRAY
Owner Business Name: UPPER ROOM AIDS MINISTRY
Authorized Representative:  PHIL GRAY
Relationship To Owner:   DIR. OF OPERATIONS


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-30AMP FIRE ALARM
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1-600AMP FIRE PUMP SER
D. 601 Up to 1200 AMPS  1  1200 AMP SERVICE SWITCH
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  4  3 SETS OF 600 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  6-100 AND 1-200
D. 3 Phase Over 225 AMPS  2  300 AMP ROOF PANEL1200AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    25  24    12               
001    55  45  22               
002    45  40  20               
003    45  40  20               
004    45  40  20               
005    45  40  20               
006    45  40    20               
Buildings Total 305  269  134                  
Total Units : 713 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/11/2013 Notice: 1 - FIRST NOTICE 10/23/2014
Power Issued: 02/11/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z138327
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/20/2014 10/23/2014 GYM A E (120) (5) Y
INSPECTION COMMENTS: (1) 1200AMP (1) 600AMP (1) 30AMP SER. SPPS
 
(2) 11/18/2014 11/25/2014 PDI C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z138327
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT ART 240.12 1200AMP SERVICE SVV. NOT CORDINATION. (FUSE TOBREAKER)
RSLV 10/20/2014 10/20/2014 11/18/2014
 
002 (999) OTHER
BSMT NO PANID HARDWARE PROVIDED FOR NEW 1200AMP SERVICE SVV. ART 110.26 (DOOR)
RSLV 10/20/2014 10/20/2014 11/18/2014
 
003 (999) OTHER
BSMT 600AMP FIRE PUMP SERVICE SVV. NO GROUND PROVIDED ART 250.64
RSLV 10/20/2014 10/20/2014 11/18/2014
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
ALL FLR NEW PANELS
RSLV 10/20/2014 10/20/2014 11/18/2014
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
6FL NO GFCT PROVIDED VACCINE ROOM 4602
RSLV 10/20/2014 10/20/2014 11/18/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back