| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
4 |
ELEVATORS |
| B. Each Additional 10 Floors Or Less |
4 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 13) |
THE CONDUCTORS FEEDING THE MOTORS ARE NOT OF PROPER SIZE (ROOF) 1P12841: CONDUCTOR FOR 30HP MOTOR NOT PROPERLY SIZED AT 125% |
OPEN |
01/26/2016 |
01/26/2016 |
|
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ROOF)BOTH MACH. RMS.: PANELS, TROUGHS AND BOXES, LIGHT FIXT. ARE NOTCOVERED |
OPEN |
01/26/2016 |
01/26/2016 |
|
| |
| 003 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ROOF) ELEV. ID # AND TAGS NOT INSTALLED ON EQUIPMENT |
OPEN |
01/26/2016 |
01/26/2016 |
|
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ROOF) MACHINE RM: NO SERVICE GFCI INSTALLED |
OPEN |
01/26/2016 |
01/26/2016 |
|
| |
| 005 |
(999) |
OTHER (ROOF) ARC FLASH WARNING STICKERS NOT INSTALLED ON EQUIPMENT |
OPEN |
01/26/2016 |
01/26/2016 |
|
| |
| 006 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (ROOF) TAP OVER 10 FT FRO SMALL PANEL 240.24 |
OPEN |
08/22/2017 |
08/22/2017 |
|
| |
| 007 |
( 19) |
DEFECTIVE WIRING IS IN USE (ROOF)2 -12 WIRES PROVIDED FOR NEUTRAL FEED SMALL PANEL 310.15 300.3 |
OPEN |
08/22/2017 |
08/22/2017 |
|
| |
| 008 |
( 19) |
DEFECTIVE WIRING IS IN USE (ROOF) 2 WIRES UNDER 1 LUG FRO CAR LIGHTS |
OPEN |
08/22/2017 |
08/22/2017 |
|
| |
| 009 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ROOF) DISCONNECT SW T OUT |
OPEN |
08/22/2017 |
08/22/2017 |
|
| |
| 010 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ROOF) EMT IN MOTOR RM NEEDS SUPPORT T OUT |
OPEN |
08/22/2017 |
08/22/2017 |
|
| |
| 011 |
(999) |
OTHER (ROOF) PLASTIC SEAL TIGHT USED TO FEED |
OPEN |
08/22/2017 |
08/22/2017 |
|
| |
| 012 |
(999) |
OTHER (ROOF) NO BOLT ON BREAKER SMALL PANEL 408.36 |
OPEN |
08/22/2017 |
08/22/2017 |
|