Electrical Application Details for App #: Z138280
Premises: 1889 BROADWAY MANHATTAN BIN: 1027465     Block: 1115   Lot: 57
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 44 W 63 ST Census Tract:   149 Health Area:  4000
ALL FLOORS SERVED, MR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   BROADWAY,    COLUMBUS AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/06/2013 5:34 PM
Application Entered:   02/06/2013 Job Start Date:   03/01/2013
Last Change:   08/22/2025 Job End Date:   03/01/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     08/22/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $872.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALAN LAPES
Owner Business Name: WEST EMPIRE ASSOCIATION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  ELEVATORS
B. Each Additional 10 Floors Or Less  4  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 08/22/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  MODERNIZATION OF ELEVATOR DEVICE #'S 1P12841, 1P12842, 1P12843 & 1P36343 BY ELEVATOR COMPANY IN CONJUNCTION WITH ELEVATOR APPLICATION. ROT-56-273018E

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z138280
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/26/2016 01/26/2016 EID V (104) (5)
INSPECTION COMMENTS: CONTRACTOR WAS LATE. NOT FULLY READY FOR INSPECTION. FULL INSPECTION NEEDED.
 
(2) 08/22/2017 08/22/2017 PHG V X (50) (7)
INSPECTION COMMENTS: CONTRACTOR NO TOOL NOT AWARE SCOPE OF WORK INSPECTED ONE MOTOR RM. FULL INSPECT NEEDED ON JOB WHEN CONTRACTOR REP KNOWS FULL SCOPE OF WORK

OBJECTION FOR APPLICATION #: Z138280
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 13) THE CONDUCTORS FEEDING THE MOTORS ARE NOT OF PROPER SIZE
(ROOF) 1P12841: CONDUCTOR FOR 30HP MOTOR NOT PROPERLY SIZED AT 125%
OPEN 01/26/2016 01/26/2016
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(ROOF)BOTH MACH. RMS.: PANELS, TROUGHS AND BOXES, LIGHT FIXT. ARE NOTCOVERED
OPEN 01/26/2016 01/26/2016
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ROOF) ELEV. ID # AND TAGS NOT INSTALLED ON EQUIPMENT
OPEN 01/26/2016 01/26/2016
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
(ROOF) MACHINE RM: NO SERVICE GFCI INSTALLED
OPEN 01/26/2016 01/26/2016
 
005 (999) OTHER
(ROOF) ARC FLASH WARNING STICKERS NOT INSTALLED ON EQUIPMENT
OPEN 01/26/2016 01/26/2016
 
006 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(ROOF) TAP OVER 10 FT FRO SMALL PANEL 240.24
OPEN 08/22/2017 08/22/2017
 
007 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF)2 -12 WIRES PROVIDED FOR NEUTRAL FEED SMALL PANEL 310.15 300.3
OPEN 08/22/2017 08/22/2017
 
008 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF) 2 WIRES UNDER 1 LUG FRO CAR LIGHTS
OPEN 08/22/2017 08/22/2017
 
009 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ROOF) DISCONNECT SW T OUT
OPEN 08/22/2017 08/22/2017
 
010 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ROOF) EMT IN MOTOR RM NEEDS SUPPORT T OUT
OPEN 08/22/2017 08/22/2017
 
011 (999) OTHER
(ROOF) PLASTIC SEAL TIGHT USED TO FEED
OPEN 08/22/2017 08/22/2017
 
012 (999) OTHER
(ROOF) NO BOLT ON BREAKER SMALL PANEL 408.36
OPEN 08/22/2017 08/22/2017