BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z138230
Premises: 80 RIVERSIDE DRIVE MANHATTAN BIN: 1033732     Block: 1244   Lot: 33
   
Application Completed and Certified

Filed: 80 RIVERSIDE DR Census Tract:   167 Health Area:  3400
1ST FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST END AVENUE,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 08/06/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/01/2013 6:13 PM
Application Entered:   02/01/2013 Job Start Date:   02/01/2013
Last Change:   08/06/2013 Job End Date:   01/28/2014
Appointment Status:   
Last Inspection By:   AGELONIAS, ANASTASIOS       On     08/01/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011769 Licensee Name: ZHENG LI
Firm: 003451 Firm Name: KJK ELECTRIC INC
Firm Phone: 917-682-3886  Firm Address: 79 BRIDGEWATER STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $47.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DON LEWIS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    12    13             
Buildings Total 12    13                
Total Units : 38 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/19/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING FOR EXISTING RESTAURANT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z138230
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/11/2013 07/19/2013 JVA A (50) (4) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 08/01/2013 08/06/2013 IOS C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z138230
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
1ST FL: 4 GANG SW BOX NOT GRNDED....... - 250.118
RSLV 07/11/2013 07/11/2013 08/01/2013
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
1ST FL: DIMMER SW GND WIRE NOT USED,CUT OFF YOLK.... - 404.9B
RSLV 07/11/2013 07/11/2013 08/01/2013
 
003 (999) OTHER
1ST FL: L F N C USED,COFFEE MAKE...... - 326.10 NYC AMMEND
RSLV 07/11/2013 07/11/2013 08/01/2013
 
004 (999) OTHER
1ST FL: NM CABLE SLEEVED IN L F N C.... - 334.12A NYC AMMEND
RSLV 07/11/2013 07/11/2013 08/01/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order