BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z138179
Premises: 334 WEST 86 STREET MANHATTAN BIN: 1033927     Block: 1247   Lot: 50
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 334 W 86 ST Census Tract:   171 Health Area:  3400
14A Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST END AVENUE,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 11/14/2024
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/29/2013 9:30 AM
Application Entered:   01/29/2013 Job Start Date:   02/01/2013
Last Change:   11/14/2024 Job End Date:   01/31/2014
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     11/14/2024      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 008866 Licensee Name: KURT SINGER
Firm: 001355 Firm Name: SINGER ELECTRIC CO.
Firm Phone: 718-548-1377  Firm Address: 169 WEST 231ST STREET BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $95.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BARBARA JERUD-LORCH
Authorized Representative:  BARBARA JERUD-LORCH
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1- 100 AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3 # 3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 POSITION
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
014  14A  12  30    20  12         
Buildings Total 12  30    20  12              
Total Units : 79 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/29/2013 Notice: 1 - FIRST NOTICE 07/13/2015
Power Issued: 01/29/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RENOVATION OF APARTMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z138179
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/03/2015 06/17/2015 BMP N (30) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 07/07/2015 07/13/2015 UMS A E (45) (6) Y
INSPECTION COMMENTS: NONE
 
(3) 11/14/2024 11/14/2024 ASK C R (15) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE. SEE MN EL EMAIL REQUEST FOR REVIEW OF THIS APP 11/14/24 8.25 AM REF TO M01111038I1EL

OBJECTION FOR APPLICATION #: Z138179
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) PANEL MISSING K/O SEAL.. 110.12A
RSLV 07/07/2015 07/07/2015 11/14/2024
 
002 (999) OTHER
(ALL FLOORS)KITCHEN COUNTERTOP RECEPTACLES SHARING SAME CIRCUITS WITH KITCHENLIGHTING OUTLETS.. 210.52
RSLV 07/07/2015 07/07/2015 11/14/2024
 
003 (999) OTHER
(ALL FLOORS)AIR HANDLERS NOT FUSED AS PER MANUFACTURES INSTRUCTIONS 15 AMP BREAK-ER NEEDED.. 110.3
RSLV 07/07/2015 07/07/2015 11/14/2024
 
004 (999) OTHER
(ALL FLOORS) 120 VOLT OUTLETS NOT A.F.C.I.PROTECTED.. 210.12
RSLV 07/07/2015 07/07/2015 11/14/2024
 
005 (999) OTHER
(ALL FLOORS) NO DISCONNECTS PROVIDED FOR CONDENSERS.. 440.14
RSLV 07/07/2015 07/07/2015 11/14/2024
 
006 (999) OTHER
(ALL FLOORS) VERTICAL RISER CONDUCTORS NOT SUPPORTED.. 300.19A
RSLV 07/07/2015 07/07/2015 11/14/2024