BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z137991
Premises: 201 WEST 85 STREET MANHATTAN BIN: 1033139     Block: 1233   Lot: 29
   
Application Completed and Certified

Filed: 201 W 85 ST Census Tract:   171 Health Area:  3400
GR. FLOOR STOR #3456 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   AMSTERDAM AVENUE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 04/30/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/10/2013 3:31 PM
Application Entered:   01/10/2013 Job Start Date:   01/17/2013
Last Change:   04/30/2013 Job End Date:   02/17/2013
Appointment Status:   
Last Inspection By:   KAFFETZAKIS, MICHAIL       On     04/22/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009165 Licensee Name: CARMINE J CAMENZULI
Firm: 003589 Firm Name: JLC ELEC'L CONTR'G INC
Firm Phone: 718-932-2499  Firm Address: 14-45 BROADWAY LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $100.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   FOR RENT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RALPH TAZAREZ
Owner Business Name: CLEO REALTY ASSOCIATES CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1X100A SVC SW
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET #2 4W
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  3456               
Buildings Total                 
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/10/2013 Notice: 1 - FIRST NOTICE 03/22/2013
Power Issued: 01/10/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z137991
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/12/2013 03/22/2013 LBI A D (30) (4) Y
INSPECTION COMMENTS: 100A SERVICE AND FEEDER TO PANEL IN STORE
 
(2) 04/22/2013 04/30/2013 MFF C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z137991
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT; NO GROUNDING ELECTRIDE CONDUCTOR CONNECTION TO WATER MAIN ATSVC 250.24(D)
RSLV 03/12/2013 03/12/2013 04/22/2013
 
002 (276) SECOND ELECTRODE NOT PROVIDED
BSMT; NO SUPPLEMENTAL ELECTRODE PROVIDED 250.53(D)(2)
RSLV 03/12/2013 03/12/2013 04/22/2013
 
003 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
BSMT; MAIN BONDING JUMPER NOT PROVIDED 250.24(B)
RSLV 03/12/2013 03/12/2013 04/22/2013
 
004 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
BSMT; IMPROPER USE OF FLOATING TONGUE LUG IN END-OF-LINE BOX AMEND110.2(B)
RSLV 03/12/2013 03/12/2013 04/22/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back