| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
3 |
1 SET 600MCM |
| D. 601 Up to 1200 AMPS |
2 |
4 SETS 350, 3 SETS 600 |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
30 |
30 SETS #6 |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
1#6, 3 #3, |
| D. 3 Phase Over 225 AMPS |
1 |
1 SET OF 350 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
1 SET OF #6 |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: 800 AMP FIRE PUMP SERVICE SW NEUTRAL BAR NOT BONDED- ART.250.28 |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 002 |
(999) |
OTHER A) BSMT: LINE AND LOAD IN THE SAME RACEWAY.... - 230.7(PULL BOX) |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 003 |
(999) |
OTHER B) BSMT: NO NEUTRAL PROVIDED 800 AMP FIRE PUMP SER SW... - 250.24B |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 004 |
(999) |
OTHER C) BSMT: FIRE PUMP SER SW IS NOT REMOTE 12" APART... - 6953.4B3 |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 005 |
(999) |
OTHER D) BSMT: FIRE PUMP SW NOT MARKED..... - 695.4B3 |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 006 |
(999) |
OTHER E) BSMT: GROUNDING CONDUCTOR IS NOT PROVIDED IN EACH SER SW- 250.64 |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 007 |
(999) |
OTHER F) ALL FLS: ARC FAULT IS NOT LISTED COMBINATION TYPE.... - 210.12 |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 008 |
(999) |
OTHER G) ALL FLS: A/C OUTLET NOT TAMPER RESISTANT.... - 406.11 |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 009 |
(999) |
OTHER H) BSMT: ARC FLASH WARNING LABELS ARE NOT PROVIDED.... - 110.16 |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 010 |
(999) |
OTHER I) BSMT: 2 100 AMP 1 200 AMP DISC SW NEUTRAL BAR BONDED AFTER SERSW....... - 250.24 |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |
| |
| 011 |
(999) |
OTHER J) BSMT: SERVICE ENTRANCE CONDUIT NOT BONDED AS PER ART.250.92A |
RSLV |
08/13/2013 |
08/13/2013 |
09/13/2013 |