Electrical Application Details for App #: Z137051
Premises: 219 WEST 70 STREET MANHATTAN BIN: 1030369     Block: 1162   Lot: 23
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 219 W 70 ST Census Tract:   159 Health Area:  3900
APPT 1 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   AMSTERDAM AVENUE,    WEST END AVENUE
Status:   C - JOB IS SIGNED OFF 12/10/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/06/2012 9:43 AM
Application Entered:   10/06/2012 Job Start Date:   10/08/2012
Last Change:   12/10/2015 Job End Date:   11/08/2012
Appointment Status:   
Last Inspection By:   URIM SYLA       On     11/23/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012204 Licensee Name: DRITAN BANUSHI
Firm: 003917 Firm Name: BRUNI ELECTRIC INC
Firm Phone: 718-729-0700  Firm Address: 37-24 24TH STREET STE 128 LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $87.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID RUBIN
Owner Business Name: ACALA PROJECTS, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  36 BREAKERS SINGLE PHASE
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  10  21  10             
Buildings Total 10  21  10                
Total Units : 51 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/07/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z137051
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/15/2013 03/23/2013 EDB A (65) (4) Y
INSPECTION COMMENTS: N/A
 
(2) 05/28/2013 06/07/2013 EDB A Y (50) (2) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(3) 11/23/2015 11/25/2015 UMS C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z137051
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (219) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:RMC)
OUTDORR; RISER 3/4 NOT PROPERLY SUPPORTED 344.30
RSLV 03/15/2013 05/28/2013 11/23/2015
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
ROOF; A/C DISCONNECT NOT PROPERLY GROUNDED 250.4A
RSLV 03/15/2013 03/15/2013 05/28/2013
 
003 (999) OTHER
ROOF; LIQIUD TIGHT MORE THAN 6' AM. 350.12
RSLV 03/15/2013 03/15/2013 05/28/2013
 
004 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
1ST FL; RECEPTICAL NOT BONDED/ GROUNDED 250.146
RSLV 03/15/2013 03/15/2013 05/28/2013
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
PANEL: A.F.C.I.NOT MATCH MANUFACTORY...... - 110.2
RSLV 05/28/2013 05/28/2013 11/23/2015
 
006 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
ROOF: A/C DISCONNECT COLOR CODE ON GND..... - 210.5
RSLV 05/28/2013 05/28/2013 11/23/2015