BIS Menu  |  Elevators  |  ECB Query for LL 158/17 Pro Cert Restriction  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z135153
Premises: 2381 FREDERICK DOUGLASS BOULEVARD MANHATTAN BIN: 1089108     Block: 1954   Lot: 36
   
Application Completed and Certified

Filed: 300 W 128 ST Census Tract:   215 Health Area:  8520
GROUND FLOOR - STORE FRONT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10027 Community Board:   110
DOB Cross Street(s):   FREDERICK DOUGLASS BOULEVARD,    ST NICHOLAS AVENUE
Status:   C - JOB IS SIGNED OFF 11/10/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/29/2012 10:04 AM
Application Entered:   05/29/2012 Job Start Date:   05/29/2012
Last Change:   11/10/2015 Job End Date:   05/29/2013
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     11/02/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012457 Licensee Name: JOSEPH A CAFIERO
Firm: 002899 Firm Name: CONTROL ELEC'L CONT'G COR
Firm Phone: 718-556-2004  Firm Address: 85 TOMPKINS STREET STATEN ISLAND NY 10304 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
011447 PALLARINO, CHRISTOPHER 002899 CONTROL ELEC'L CONT'G COR RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $313.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   MEDICAL OFFICE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRETT BERN
Owner Business Name: THE BERN COMPANY
Authorized Representative:  DAVID SCHAFER
Relationship To Owner:   GENERAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  1  1 - 400 AMP PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    65  120    20  63  10  25     
Buildings Total 65  120    20  63     10     25      
Total Units : 303 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/26/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  #4400 2381 FREDRICK DOUGLAS BLVD

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z135153
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/04/2012 10/18/2012 CLC A (45) (2) Y
INSPECTION COMMENTS: SEE OBJECTIONS
 
(2) 04/18/2013 04/26/2013 GYM A R (60) (4) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(3) 11/02/2015 11/10/2015 GYM C R (70) (0) Y
INSPECTION COMMENTS: 1 200 AMP,1 400 AMP PANELS,1 500 MCM FEEDER

OBJECTION FOR APPLICATION #: Z135153
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1ST FL: MULTI WIRES NOT UNDER 2 POLE BREAKERS... - 210.4
RSLV 10/04/2012 10/04/2012 04/18/2013
 
002 (999) OTHER
1ST FL: THROUGH-OUT LIGHT FIXTURES EQUIPMENT GND NOT PROVIDED INNIPPS..... - 250.118(6)(B)
RSLV 10/04/2012 10/04/2012 04/18/2013
 
003 (999) OTHER
1ST FL: METAL RACEWAY IS NOT PROVIDED FOR PATIENT CARE AREA (10)EXAMROOMS.... - ART 517.13...CONTRACTOR USED MC METAL CLAD CABLE
RSLV 04/18/2013 04/18/2013 11/02/2015
 
004 (999) OTHER
A) 1ST FL: ART.250.122 ALUMINUM MC METAL CLAD CABLE USED FROM NEWPANEL TO SPLICE BOXES CEILING (10) EXAM ROOMS
RSLV 04/18/2013 04/18/2013 11/02/2015
 
005 ( 17) DEFECTIVE SWITCHES ARE IN USE
1ST FL: 20 AMP BREAKERS
RSLV 04/18/2013 04/18/2013 11/02/2015
 
006 (999) OTHER
1ST FL: ALUMINUM MC METAL CLAD CABLE OUTLET BOXES ARE NOT BONDED
RSLV 04/18/2013 04/18/2013 11/02/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  ECB Query for LL 158/17 Pro Cert Restriction  |  Electrical Inspection Work Order  |  Back