BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z134729
Premises: 3612 BROADWAY MANHATTAN BIN: 1062060     Block: 2080   Lot: 59
   
Application Completed and Certified

Filed: 3612 BROADWAY Census Tract:   233 Health Area:  0620
STREET LEVEL Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10031 Community Board:   109
Special Place Name:   SOUTH HOSPITALITY GROUP
Related Job Number:    120907947
DOB Cross Street(s):   WEST 148 STREET,    WEST 149 STREET
Status:   C - JOB IS SIGNED OFF 12/06/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/30/2012 10:27 AM
Application Entered:   04/30/2012 Job Start Date:   04/30/2012
Last Change:   12/06/2012 Job End Date:   07/15/2012
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     11/27/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011018 Licensee Name: LUIS M JIMENEZ
Firm: 002356 Firm Name: L J ELEC'L SERV. INC.
Firm Phone: 718-239-8970  Firm Address: 1408 ROSEDALE AVENUE BRONX NY 10472 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $71.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LAUREN LYNCH
Owner Business Name: SOUTH HOSPITALITY GROUP
Authorized Representative:  LAUREN LYNCH
Relationship To Owner:   TENANT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  12 CIR
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  COM  15  31    15         
Buildings Total 15  31    15              
Total Units : 75 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/18/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JUST WIRING FOR LIGHT AND POWER, SERVICE IS EXISTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z134729
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/04/2012 10/18/2012 TSO A (30) (4) Y
INSPECTION COMMENTS: SEE OBJECTIONS
 
(2) 11/27/2012 12/06/2012 TSO C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z134729
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: NO DISCONNECT 2 WALK-IN BOX...... - 440.14
RSLV 10/04/2012 10/04/2012 11/27/2012
 
002 (999) OTHER
1FL: MULTI WIRE BRANCH CIR NEED HANDLE TIE...... - 210.4
RSLV 10/04/2012 10/04/2012 11/27/2012
 
003 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
BSMT: EXTENSION CORD USED AS PERMANENT WIRING WALK-IN BOX
RSLV 10/04/2012 10/04/2012 11/27/2012
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
ATTIC: OPEN BOX COVER ATTIC
RSLV 10/04/2012 10/04/2012 11/27/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order