BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z134335
Premises: 27 WEST 72 STREET MANHATTAN BIN: 1087511     Block: 1125   Lot: 7502
   
Application Completed and Certified

Filed: 27 W 72 ST Census Tract:   157 Health Area:  4000
APT 1402 1502 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK EXIT WEST 72 ST,    COLUMBUS AVENUE
Status:   C - JOB IS SIGNED OFF 07/29/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/28/2012 10:05 AM
Application Entered:   03/28/2012 Job Start Date:   04/03/2012
Last Change:   07/29/2013 Job End Date:   10/21/2012
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     07/12/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011720 Licensee Name: ERIC K AU
Firm: 003306 Firm Name: ERIC & NG ELEC'L, INC.
Firm Phone: 212-673-4118  Firm Address: 155 SUFFOLK STREET NEW YORK NY 10002 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $280.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FRANKFORT TAMARA
Owner Business Name: OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  3  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
014  1402  96  40  25  96             
015  1502  96  40  25  96             
Buildings Total 192  80  50  192                
Total Units : 520 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/14/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z134335
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/21/2012 08/07/2012 JSB Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 05/02/2013 05/13/2013 TSO A (45) (5) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(3) 06/06/2013 06/14/2013 JTE A R (25) (1) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(4) 07/12/2013 07/23/2013 EDB C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z134335
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
NO A.F.C.I.FOR AV RACK....... - 210.12
RSLV 05/02/2013 05/02/2013 06/06/2013
 
002 (999) OTHER
NO BOND ON AV RACK...... - 640.22
RSLV 05/02/2013 05/02/2013 06/06/2013
 
003 (999) OTHER
WINDOW SHADES NOT A.F.C.I.PROTECTED..... - 210.12
RSLV 05/02/2013 05/02/2013 06/06/2013
 
004 (999) OTHER
A.F.C.I.T-OUT........ - 210.12
RSLV 05/02/2013 05/02/2013 06/06/2013
 
005 (999) OTHER
A.F.C.I.NOT COMBO TYPE....... - 210.12
RSLV 05/02/2013 05/02/2013 06/06/2013
 
006 ( 19) DEFECTIVE WIRING IS IN USE
ALL PANELS: MULTIWIRE 12-3 CKTS NEED 2 POLE COMBO A.F.C.I.BKR TYPE
RSLV 06/06/2013 06/06/2013 07/12/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back