| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400AMPS/RES./ |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
1 |
3000AMPS /FEEDER EXISTS/ |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
10 |
500MCM /RES. RISER/ |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
30 |
200 AMPS LP |
| D. 3 Phase Over 225 AMPS |
6 |
600 AMPS DP /EMDP |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BASEMENT 200 AMP SIEMENS SPECIAL SERVICE FIRE PUMP NOT AS PERDRAWING110.2 |
RSLV |
02/25/2015 |
05/01/2015 |
10/29/2015 |
| |
| 002 |
(999) |
OTHER BASEMENT DOORS NO PANIC HARDWARE PROVIDED ART. 110.26 |
RSLV |
02/25/2015 |
02/25/2015 |
05/01/2015 |
| |
| 003 |
(999) |
OTHER BASEMENT NO TAMPER PROOF HARDWARE PROVIDED AS PER DRAWING |
RSLV |
02/25/2015 |
02/25/2015 |
05/01/2015 |
| |
| 004 |
(999) |
OTHER BASEMENT MDP NOT AS PER DRAWING ART. 110.2 |
RSLV |
02/25/2015 |
05/01/2015 |
10/29/2015 |
| |
| 005 |
(999) |
OTHER BASEMENT GROUNDING RACEWAY HANDING JUMPER UNDER SIZE TAB 250.66 |
RSLV |
02/25/2015 |
05/01/2015 |
10/29/2015 |
| |
| 006 |
(999) |
OTHER BLDG STEELOUNDING ELECTRODE CONDUCTOR UNDER SIZE TAB. 250 |
RSLV |
02/25/2015 |
02/25/2015 |
05/01/2015 |
| |
| 007 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED ALL FLOORS ELECTRIC CLOSET ARMORED CABLE |
RSLV |
02/25/2015 |
02/25/2015 |
05/01/2015 |
| |
| 008 |
(999) |
OTHER 18,19 FLOORS AFCI MUST PROECT ENTIRE BRANCH CIRCUITS ART. 210.12PENT HOUSE SUITE) |
RSLV |
02/25/2015 |
05/01/2015 |
10/29/2015 |
| |
| 009 |
(999) |
OTHER 18,19 FLOORS RECEPTACLE NOT LISTED TAMPER RESISTANT TYPE ART 406.11(PENTHOUSE SUITE) |
RSLV |
02/25/2015 |
05/01/2015 |
10/29/2015 |
| |
| 010 |
(999) |
OTHER 18,19 FLOORS MIN 2-20A SMALL APPLIANE CIRCUITS REQ'D ART 210.11(PENTGIYSE SUITE) |
RSLV |
02/25/2015 |
05/01/2015 |
10/29/2015 |
| |
| 011 |
(999) |
OTHER 18,19, FLOORS SEPARATE 20A CIRCUIT FOR BATH RECEPTS ART. 210.11(PENTHOUSE SUITE) |
RSLV |
02/25/2015 |
05/01/2015 |
10/29/2015 |
| |
| 012 |
(999) |
OTHER ROOF EM-DP NOT INSTALLED AS PER DRAWING ART. 110.2 |
RSLV |
02/25/2015 |
02/25/2015 |
05/01/2015 |
| |
| 013 |
(999) |
OTHER BASEMENT 1-300 MCM 1#4 GROUND IN 1 3" CONDUIT NOT AS PER DRAWING110.2 |
RSLV |
02/25/2015 |
05/01/2015 |
10/29/2015 |
| |
| 014 |
(999) |
OTHER ROOF SPECIAL SERVICE F.P NOT INSTALLED AS PER DRAWING 110.2 |
RSLV |
02/25/2015 |
05/01/2015 |
10/29/2015 |
| |
| 015 |
(999) |
OTHER 1515RS METER BANKS 6 POSITIONS 5-2 90 AMP QPH 1-2P 70Q PH BREAKERSNOT AS PER DRAWING 110.2 |
RSLV |
05/01/2015 |
05/01/2015 |
10/29/2015 |
| |
| 016 |
(999) |
OTHER A)BASEMENT FROM CON-EDISON BAULT TO 1200 ANO SERVUCE SW.3 SETS 500MCM IS NOT INSTALLED AS PER DRAWING 110.2 |
RSLV |
05/01/2015 |
05/01/2015 |
10/29/2015 |
| |
| 017 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE BASEMENT 3 SETS OF 500 MCM FEEDERS PROTECTED 12OOAMP |
RSLV |
05/01/2015 |
05/01/2015 |
10/29/2015 |
| |
| 018 |
(999) |
OTHER B)15+5 FLOOR JUNCTION BOX NOT ACCESSIBLE ART. 314.29 |
RSLV |
05/01/2015 |
05/01/2015 |
10/29/2015 |
| |
| 019 |
(999) |
OTHER C)BASEMENT 2 4" X 1/4 CU PHASE AND NEUTRAL NOT AS PER DRAWING ART110.2 |
RSLV |
05/01/2015 |
05/01/2015 |
10/29/2015 |
| |
| 020 |
(999) |
OTHER D)BASEMENT 200AMP SPECIAL SER. F.P 1-SET 300 MUN SER ENT. CONDUCTORNOT INSTALLED AS PER DRAWING ART. 110.2 |
RSLV |
05/01/2015 |
05/01/2015 |
10/29/2015 |
| |
| 021 |
(999) |
OTHER E)BASEMENT SPECIAL SERVICE F.P CONNECTION NOT LINE SIDE OF SERVICEENT. AS PER DRAWING ART 110.2 |
RSLV |
05/01/2015 |
05/01/2015 |
10/29/2015 |