BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z134097
Premises: 101 WEST 57 STREET MANHATTAN BIN: 1023730     Block: 1010   Lot: 29
   
Application Completed and Certified

Filed: 101 W 57 ST Census Tract:   137 Health Area:  4700
BSMT THRU 19TH FLOOR AND ROOF Admin Area:   Z - UPPER MANHATTAN Inspection Area:   F
NEW YORK, NY 10019 Community Board:   105
Special Place Name:   BUCKINGHAM HOTEL
Related Job Number:    120086762
DOB Cross Street(s):   AVENUE OF THE AMERICAS,    6 1/2 AVENUE
Status:   C - JOB IS SIGNED OFF 11/30/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/12/2012 3:35 PM
Application Entered:   03/12/2012 Job Start Date:   03/13/2012
Last Change:   11/30/2015 Job End Date:   03/07/2013
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     10/29/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011399 Licensee Name: JEFF SKOWRONSKI
Firm: 002489 Firm Name: INTER CONNECTION ELETRIC
Firm Phone: 718-748-9800  Firm Address: 209 GRANITE AVE STATEN ISLAND NY 10303 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   50831/11A0301
Owner / Occup: GARY ZIMBERG
Owner Business Name: THE JAMES HOTEL GROUP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400AMPS/RES./
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  3000AMPS /FEEDER EXISTS/
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  10  500MCM /RES. RISER/
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  30  200 AMPS LP
D. 3 Phase Over 225 AMPS  6  600 AMPS DP /EMDP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  BSMT  12               
BAL  EXT  179    179             
001  1FL  139  21    139             
002  2FL  174  39    12  174             
003  3FL  224  134  16  96  224             
004  4FL  249  134  17  96  249             
005  5FL  249  134  17  96  249             
006  6FL  249  134  17  96  249             
007  7FL  249  134  17  96  249             
008  8FL  249  134  17  96  249             
009  9FL  249  134  17  96  249             
010  10FL  249  134  17  96  249             
011  11FL  249  134  17  96  249             
012  12FL  249  134  17  96  249             
014  14FL  249  134  17  96  249             
015  15FL  249  134  17  96  249             
016  16FL  249  134  17  96  249             
017  17FL  12  20  12             
ROF  18/19  35  32  35  200         
Buildings Total 3758  1870  228  1284  3758     200           
Total Units : 11098 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 4 + New Meters 1 - Removed Meters 0 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/12/2012 Notice: 1 - FIRST NOTICE 05/07/2015
Power Issued: 03/12/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z134097
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/25/2015 03/03/2015 GYM V E (270) (14) Y
INSPECTION COMMENTS: INSPECTED PENTHOUSE SUITE, 1503, 1507 ROOM ONLY. 1-3000AMP 1-400AMP SERVICE SWS
 
(2) 04/17/2015 04/23/2015 ECH Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 05/01/2015 05/07/2015 GYM A Y E (120) (7) Y
INSPECTION COMMENTS: CALENDAR NO 50831 REV 3
 
(4) 10/29/2015 11/30/2015 ECH C R E (300) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z134097
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT 200 AMP SIEMENS SPECIAL SERVICE FIRE PUMP NOT AS PERDRAWING110.2
RSLV 02/25/2015 05/01/2015 10/29/2015
 
002 (999) OTHER
BASEMENT DOORS NO PANIC HARDWARE PROVIDED ART. 110.26
RSLV 02/25/2015 02/25/2015 05/01/2015
 
003 (999) OTHER
BASEMENT NO TAMPER PROOF HARDWARE PROVIDED AS PER DRAWING
RSLV 02/25/2015 02/25/2015 05/01/2015
 
004 (999) OTHER
BASEMENT MDP NOT AS PER DRAWING ART. 110.2
RSLV 02/25/2015 05/01/2015 10/29/2015
 
005 (999) OTHER
BASEMENT GROUNDING RACEWAY HANDING JUMPER UNDER SIZE TAB 250.66
RSLV 02/25/2015 05/01/2015 10/29/2015
 
006 (999) OTHER
BLDG STEELOUNDING ELECTRODE CONDUCTOR UNDER SIZE TAB. 250
RSLV 02/25/2015 02/25/2015 05/01/2015
 
007 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
ALL FLOORS ELECTRIC CLOSET ARMORED CABLE
RSLV 02/25/2015 02/25/2015 05/01/2015
 
008 (999) OTHER
18,19 FLOORS AFCI MUST PROECT ENTIRE BRANCH CIRCUITS ART. 210.12PENT HOUSE SUITE)
RSLV 02/25/2015 05/01/2015 10/29/2015
 
009 (999) OTHER
18,19 FLOORS RECEPTACLE NOT LISTED TAMPER RESISTANT TYPE ART 406.11(PENTHOUSE SUITE)
RSLV 02/25/2015 05/01/2015 10/29/2015
 
010 (999) OTHER
18,19 FLOORS MIN 2-20A SMALL APPLIANE CIRCUITS REQ'D ART 210.11(PENTGIYSE SUITE)
RSLV 02/25/2015 05/01/2015 10/29/2015
 
011 (999) OTHER
18,19, FLOORS SEPARATE 20A CIRCUIT FOR BATH RECEPTS ART. 210.11(PENTHOUSE SUITE)
RSLV 02/25/2015 05/01/2015 10/29/2015
 
012 (999) OTHER
ROOF EM-DP NOT INSTALLED AS PER DRAWING ART. 110.2
RSLV 02/25/2015 02/25/2015 05/01/2015
 
013 (999) OTHER
BASEMENT 1-300 MCM 1#4 GROUND IN 1 3" CONDUIT NOT AS PER DRAWING110.2
RSLV 02/25/2015 05/01/2015 10/29/2015
 
014 (999) OTHER
ROOF SPECIAL SERVICE F.P NOT INSTALLED AS PER DRAWING 110.2
RSLV 02/25/2015 05/01/2015 10/29/2015
 
015 (999) OTHER
1515RS METER BANKS 6 POSITIONS 5-2 90 AMP QPH 1-2P 70Q PH BREAKERSNOT AS PER DRAWING 110.2
RSLV 05/01/2015 05/01/2015 10/29/2015
 
016 (999) OTHER
A)BASEMENT FROM CON-EDISON BAULT TO 1200 ANO SERVUCE SW.3 SETS 500MCM IS NOT INSTALLED AS PER DRAWING 110.2
RSLV 05/01/2015 05/01/2015 10/29/2015
 
017 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BASEMENT 3 SETS OF 500 MCM FEEDERS PROTECTED 12OOAMP
RSLV 05/01/2015 05/01/2015 10/29/2015
 
018 (999) OTHER
B)15+5 FLOOR JUNCTION BOX NOT ACCESSIBLE ART. 314.29
RSLV 05/01/2015 05/01/2015 10/29/2015
 
019 (999) OTHER
C)BASEMENT 2 4" X 1/4 CU PHASE AND NEUTRAL NOT AS PER DRAWING ART110.2
RSLV 05/01/2015 05/01/2015 10/29/2015
 
020 (999) OTHER
D)BASEMENT 200AMP SPECIAL SER. F.P 1-SET 300 MUN SER ENT. CONDUCTORNOT INSTALLED AS PER DRAWING ART. 110.2
RSLV 05/01/2015 05/01/2015 10/29/2015
 
021 (999) OTHER
E)BASEMENT SPECIAL SERVICE F.P CONNECTION NOT LINE SIDE OF SERVICEENT. AS PER DRAWING ART 110.2
RSLV 05/01/2015 05/01/2015 10/29/2015