BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z133782
Premises: 112 WEST 79 STREET MANHATTAN BIN: 1030260     Block: 1150   Lot: 37
   
Application Completed and Certified

Filed: 118 W 79 ST Census Tract:   165 Health Area:  3500
APT 14A Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   C - JOB IS SIGNED OFF 04/17/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/15/2012 9:52 AM
Application Entered:   02/15/2012 Job Start Date:   02/16/2012
Last Change:   04/17/2013 Job End Date:   02/20/2013
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     04/03/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012192 Licensee Name: JOHN RYAN
Firm: 003247 Firm Name: MONTGOMERY ELEC'L CONTR'G
Firm Phone: 718-994-8026  Firm Address: 4250 VAN CORTLAND PARK EAST CORP. BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $67.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SUSAN BROWN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    38  54    28               
Buildings Total 38  54    28                  
Total Units : 120 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/16/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z133782
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/17/2012 05/31/2012 CLC J (30) (0) Y
INSPECTION COMMENTS: JOB IN ROUGHING STATE
 
(2) 10/24/2012 11/16/2012 EDB A (60) (4) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(3) 04/03/2013 04/17/2013 EDB C R (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z133782
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (229) SPLICE BOXES NOT ACCESSIBLE
KITCHEN: G.F.C.I.NOT ACCESSOBLE(UNDER SINK ISLAND)..... - 314.29
RSLV 10/24/2012 10/24/2012 04/03/2013
 
002 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
ALL 14A: RECEPTACLE NOT BONDED/GROUNDED....... - 250.146
RSLV 10/24/2012 10/24/2012 04/03/2013
 
003 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
BATHROOM: LIGHT FIXTURE NOT APPROVED...... - 410.10
RSLV 10/24/2012 10/24/2012 04/03/2013
 
004 (999) OTHER
KITCHEN: PANEL MULTIWIRE NOT GROUPED NOT SIMULTANIOUS TRIP.. - 210.4
RSLV 10/24/2012 10/24/2012 04/03/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back