BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z133296
Premises: 1 WEST 72 STREET MANHATTAN BIN: 1028637     Block: 1125   Lot: 25
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1 W 72 ST Census Tract:   157 Health Area:  4000
APARTMENT 54 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK EXIT WEST 72 ST,    COLUMBUS AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/03/2012 3:25 PM
Application Entered:   01/03/2012 Job Start Date:   01/03/2012
Last Change:   08/22/2025 Job End Date:   12/12/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     01/08/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011935 Licensee Name: MATTHEW J PETERS
Firm: 003566 Firm Name: HAMPTON ELECTRICAL CORP
Firm Phone: 646-485-5086  Firm Address: 32 EAST 31ST ST.-SUITE 850 NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $210.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BENJAMIN DOLLER
Authorized Representative:  CHRISTIAN RICCI
Relationship To Owner:   ARCHITECT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  100 AMP
C. 3 Phase Up to 225 AMPS  1  200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  54  40  57  18  38             
Buildings Total 40  57  18  38                
Total Units : 160 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 01/03/2012 Notice: 1 - FIRST NOTICE 01/16/2013
Power Issued: 01/03/2012 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z133296
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/08/2013 01/16/2013 EDB A E (55) (3) Y
INSPECTION COMMENTS: *SEE OBJECTIONS

OBJECTION FOR APPLICATION #: Z133296
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (340) RECEPTACLES NOT TAMPERPROOF
54: KITCHEN RECEPTICLE NOT TAMPER PROOF....... - 406.11
OPEN 01/08/2013 01/08/2013
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
PANEL: K/O MISSING
OPEN 01/08/2013 01/08/2013
 
003 (999) OTHER
PANEL: MULTIWIRE CKT NO GROUPED,NO SIMULTANIOUS TRIP.... - 210.4
OPEN 01/08/2013 01/08/2013