BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
Building Overview Work Items |
QUANTITY |
DESCRIPTION |
SERVICE SWITCHES |
|
A. Up to 100 AMPS |
0 |
|
B. 101 Up to 200 AMPS |
0 |
|
C. 201 Up to 600 AMPS |
0 |
|
D. 601 Up to 1200 AMPS |
0 |
|
E. Over 1200 AMPS |
0 |
|
SER. ENT. & FDR COND (EACH SET) |
|
A. Up to #2 CONDUCTOR |
0 |
|
B. Over #2 to 1/0 |
0 |
|
C. Over 1/0 to 250 MCM |
0 |
|
D. Over 250 MCM |
0 |
|
PANELS |
|
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
C. 3 Phase Up to 225 AMPS |
0 |
|
D. 3 Phase Over 225 AMPS |
0 |
|
ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
A. Total No. of Elevators / Escalators / Material Lifts |
3 |
3-39 STOP ELEVATOR STOPS |
B. Each Additional 10 Floors Or Less |
9 |
|
BOILER CONTROLS |
0 |
|
OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
|
001 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE (BASEMENT) PITS LIGHTS. |
OPEN |
06/04/2019 |
06/04/2019 |
|
|
002 |
( 29) |
OUTLET BOXES ARE NOT COVERED (BASEMENT) PITS & MACHINE ROOMS TOP OF CAB. |
OPEN |
06/04/2019 |
06/04/2019 |
|
|
003 |
( 30) |
OUTLET BOXES ARE NOT SECURED (BASEMENT) ELEVATOR PITS & MACHINES ROOM. |
OPEN |
06/04/2019 |
06/04/2019 |
|
|
004 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (BASEMENT) ELEVATOR MACHINE & PITS |
OPEN |
06/04/2019 |
06/04/2019 |
|
|
005 |
(999) |
OTHER (BASEMENT) NO GFCI OUTLETS PITS 620.85 |
OPEN |
06/04/2019 |
06/04/2019 |
|
|
006 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH (ROOF) CONTROLLER PANENS |
OPEN |
06/04/2019 |
06/04/2019 |
|
|
007 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (ROOF) MACHINE ROOM. |
OPEN |
06/04/2019 |
06/04/2019 |
|
|
008 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (ROOF) MACHINE ROOM |
OPEN |
06/04/2019 |
06/04/2019 |
|
|
009 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (ROOF) ELEVATOR DISC SWITCHES. |
OPEN |
06/04/2019 |
06/04/2019 |
|
|
010 |
(999) |
OTHER (ROOF) ELEVATORS MACHINE ROOM RACEWAY NOT PROPERLY BONDED 620.81 |
OPEN |
06/04/2019 |
06/04/2019 |
|