BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z133049
Premises: 747 10 AVENUE MANHATTAN BIN: 1083800     Block: 1079   Lot: 29
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 747 TENTH AV Census Tract:   135 Health Area:  4500
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   G
NEW YORK, NY 10019 Community Board:   104
DOB Cross Street(s):   WEST 50 STREET,    WEST 51 STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 06/04/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/13/2011 2:42 PM
Application Entered:   12/13/2011 Job Start Date:   12/13/2011
Last Change:   06/04/2019 Job End Date:   07/01/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     06/04/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010645 Licensee Name: RUSSELL DYSON
Firm: 002216 Firm Name: E.S.B. ELECTRIC CORP.
Firm Phone: 718-381-8800  Firm Address: 43-16 12TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $1,162.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EPHRAIM FRUCHTHANDIER
Owner Business Name: HUDSON VIEW TERRACE EMPIR
Authorized Representative:  EPHRAIM FRUCHTHANDIER
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  3  3-39 STOP ELEVATOR STOPS
B. Each Additional 10 Floors Or Less  9  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/04/2019
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  ELEVATORS (1) IP 31000 / (2) IP 31001 (3) IP 31002

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z133049
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/04/2019 06/04/2019 GYM V (195) (10)
INSPECTION COMMENTS: OBJECTIONS.

OBJECTION FOR APPLICATION #: Z133049
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(BASEMENT) PITS LIGHTS.
OPEN 06/04/2019 06/04/2019
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) PITS & MACHINE ROOMS TOP OF CAB.
OPEN 06/04/2019 06/04/2019
 
003 ( 30) OUTLET BOXES ARE NOT SECURED
(BASEMENT) ELEVATOR PITS & MACHINES ROOM.
OPEN 06/04/2019 06/04/2019
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) ELEVATOR MACHINE & PITS
OPEN 06/04/2019 06/04/2019
 
005 (999) OTHER
(BASEMENT) NO GFCI OUTLETS PITS 620.85
OPEN 06/04/2019 06/04/2019
 
006 (220) DOUBLE LUGGING IN SERVICE SWITCH
(ROOF) CONTROLLER PANENS
OPEN 06/04/2019 06/04/2019
 
007 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(ROOF) MACHINE ROOM.
OPEN 06/04/2019 06/04/2019
 
008 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(ROOF) MACHINE ROOM
OPEN 06/04/2019 06/04/2019
 
009 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(ROOF) ELEVATOR DISC SWITCHES.
OPEN 06/04/2019 06/04/2019
 
010 (999) OTHER
(ROOF) ELEVATORS MACHINE ROOM RACEWAY NOT PROPERLY BONDED 620.81
OPEN 06/04/2019 06/04/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order