BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z132298
Premises: 600 WEST 189 STREET MANHATTAN BIN: 1064011     Block: 2168   Lot: 46
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1573 ST NICHOLAS AV Census Tract:   279 Health Area:  0221
CROSS ST WEST 188 ST Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10040 Community Board:   112
Special Place Name:   AMPANADAS MONUMENTAL
DOB Cross Street(s):   WEST 188 STREET,    WEST 189 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/14/2011 8:56 PM
Application Entered:   10/14/2011 Job Start Date:   10/17/2011
Last Change:   08/22/2025 Job End Date:   12/17/2011
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     01/28/2014      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  X - NOT REMOVED

License #: 011129 Licensee Name: JESUS M CORPORAN
Firm: 002506 Firm Name: JECO ELEC'L SERVICE CORP.
Firm Phone: 718-542-1931  Firm Address: 1162 INTERVALE AVENUE BRONX NY 10459 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $216.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CARLOS R DOMINGUEZ
Owner Business Name: EMPANADAS MONUMENTAL
Authorized Representative:  CARLOS DOMINGUEZ
Relationship To Owner:   TENANT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMPS 3 PHASE
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  4 WIERE NO 2\0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  30 POSITIONS 3 PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  STORE  10  12  10             
Buildings Total 10  12  10                
Total Units : 37 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 10/14/2011 Notice: C - CALL TO OFFICE 02/04/2014
Power Issued: 10/14/2011 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z132298
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/29/2011 01/12/2012 GYM V G (55) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 01/28/2014 02/04/2014 GYM V X G (35) (3) Y
INSPECTION COMMENTS: SEE APPLICATION NO.Z139257

OBJECTION FOR APPLICATION #: Z132298
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTSIDE: CANOPY LIGHTS
OPEN 12/29/2011 01/28/2014
 
002 (999) OTHER
1ST FL: OUTLET BOXES NOT AS PER ART.250.146
OPEN 12/29/2011 01/28/2014
 
003 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
OUTSIDE: CANOPY LIGHTS BRANCH CIRCUIT WIRING
OPEN 12/29/2011 01/28/2014
 
004 (999) OTHER
BSMT: DEFECTIVE GROUND CLAMP AT WATER MAIN. ART.250.21
OPEN 01/28/2014 01/28/2014
 
005 (999) OTHER
A) BSMT: MORE THAN SIX SERVICE SWS PROVIDED. 230.71
OPEN 01/28/2014 01/28/2014
 
006 (999) OTHER
B) BSMT: NO WATER MAIN GROUNDING ELECTRODE CONDUCTOR PROVIDED INSERVICE SW. 250.66
OPEN 01/28/2014 01/28/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.