BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z132020
Premises: 155 WEST 88 STREET MANHATTAN BIN: 1032292     Block: 1219   Lot: 14
   
Application Completed and Certified

Filed: 155 W 88 ST Census Tract:   173 Health Area:  3220
ENTIRE BUILDING Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
Related Job Number:    120539444
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   C - JOB IS SIGNED OFF 08/30/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/22/2011 7:18 PM
Application Entered:   09/22/2011 Job Start Date:   09/23/2011
Last Change:   08/30/2013 Job End Date:   09/22/2012
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     08/23/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011392 Licensee Name: HOWARD M LEUNG
Firm: 003536 Firm Name: AERO ELECTRIC CORP
Firm Phone: 212-673-4383  Firm Address: 78 FORSYTH STREET, STE 1 NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $296.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT JR. WHITE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1 200A SWITCH
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  3 SET OF UP TO #2 WIRE
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 SET OF #3/0 WIRE
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  3 100A PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1 200A PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS               
001    21  15             
002    18  15  18             
003    24  17             
Buildings Total 69  33  56                
Total Units : 174 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 4 + New Meters 1 - Removed Meters 4 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/22/2011 Notice: 1 - FIRST NOTICE 08/06/2013
Power Issued: 09/22/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NYC2005 ELECTRICAL CODE. OWNER WANTS TO CONVERT THE BUILDING INTO A SINGLE FAMILY HOME

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z132020
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/14/2012 08/02/2012 RPL Z (0) (0) Y
INSPECTION COMMENTS: N/A
 
(2) 08/01/2013 08/06/2013 IOS A E (45) (3) Y
INSPECTION COMMENTS: *NO ACCESS TO ROOF* **SEE OBJECTIONS
 
(3) 08/23/2013 08/30/2013 DNM C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z132020
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
LIGHT FIXTURE ON TOP OF SHOWER IN SECOND FLOOR BATHROOM NOT VAPORPROOF
RSLV 08/01/2013 08/01/2013 08/23/2013
 
002 (999) OTHER
RECEPTACLES IN BASEMENT NOT A.F.C.I.PROTECTED.... - 210.8
RSLV 08/01/2013 08/01/2013 08/23/2013
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
EMT BELOW END LINE BOX NOT SUPPORTED
RSLV 08/01/2013 08/01/2013 08/23/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.