Electrical Application Details for App #: Z131587
Premises: 69 WEST 71 STREET MANHATTAN BIN: 1079296     Block: 1124   Lot: 3
   
Application Completed and Certified

Filed: 69 W 71 ST Census Tract:   157 Health Area:  4000
COLUMBUS AVENUE Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK WEST,    COLUMBUS AVENUE
Status:   C - JOB IS SIGNED OFF 01/24/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/17/2011 10:33 AM
Application Entered:   08/17/2011 Job Start Date:   08/20/2011
Last Change:   01/24/2013 Job End Date:   12/19/2012
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     10/17/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012057 Licensee Name: MIKHAIL LEYBMAN
Firm: 003746 Firm Name: RELIABLE ELEC'L CONTR'S
Firm Phone: 347-987-3221  Firm Address: 167 7TH STREET INC BROOKLYN NY 11215 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $1,245.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (5  Stores, 53 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: AHARON VACHNIN
Owner Business Name: 71 REALTY ASSOCCIATES LLC
Authorized Representative:  AHARON VACHNIN
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  7  200AMP - 7PCS.
C. 201 Up to 600 AMPS  4  400AMP -3PCS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  4SETS OF 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  4PCS -200AMP 3PH
D. 3 Phase Over 225 AMPS  1  1PC - 400AMP 3PH
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 3 #10-Wire 3
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/17/2011 Notice: 1 - FIRST NOTICE 08/28/2012
Power Issued: 08/17/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z131587
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/16/2012 08/28/2012 JSB V E (45) (4) Y
INSPECTION COMMENTS: *CONTRACTOR NO SHOW*
 
(2) 10/17/2012 11/08/2012 DAH C R E (75) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z131587
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT: GRD ELECTRODE NOT WITHIN 5'OF BLDG ENTRANCE
RSLV 08/16/2012 08/16/2012 10/17/2012
 
002 (999) OTHER
BSMT: FLANGE TO TROUGH CONNECTION NOT PROPERLY INSTALLED THROUGH-OUTBASEMENT......... - 366.100(C)
RSLV 08/16/2012 08/16/2012 10/17/2012
 
003 (999) OTHER
BSMT: SVC AND DIST EQUIP NOT PROPERLY LABELED..... - 110.22
RSLV 08/16/2012 08/16/2012 10/17/2012
 
004 (999) OTHER
BSMT: NO SUPPLEMENTAL GRD PROVIDED .... - 250.53(E)
RSLV 08/16/2012 08/16/2012 10/17/2012