| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
1 |
2000 AMP SWITCH |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
SETS OF 3/0 WIRE |
| D. Over 250 MCM |
5 |
SETS 500 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
42 CIRCUITS |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER ELECTRIC RM CEILING 6X6 JUNCTIONHAS NO COVER 314-28C |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |
| |
| 002 |
( 55) |
CONDUCTORS SMALLER THAN 1/0 AWG HAVE BEEN RUN IN PARALLEL ELECTRIC RM KO ARE NOT CLOSED CEILING OUTLET BOXES |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |
| |
| 003 |
( 29) |
OUTLET BOXES ARE NOT COVERED ELECTRIC RM OUTLET BOXES ARE NOT COVERED TOP OF SW |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |
| |
| 004 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED ELECTRIC RM ARMORED CABLE NOT PROPERLY SECURED |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |
| |
| 005 |
( 36) |
CONDUCTORS ARE NOT PROPERLY COLOR CODED ELECTRIC RM CONDUCTORS ARE NOT PROPERLY COLOR CODED FROM 12X12SPLICE BOX TO 200A PANEL(CONDUCTORS TAPE) |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |
| |
| 006 |
(999) |
OTHER ELECT RM DOUBLE LUGGING IN 12X24 PLICE BOX 110.14A |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |
| |
| 007 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER ELECTRIC RM SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |
| |
| 008 |
(999) |
OTHER ELE RM GROUNDING ELECTRODE CONDUCTOR NOT CONTINOUS 250.64(C) |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |
| |
| 009 |
(999) |
OTHER ELECTRIC RM NO FUSE COORDINATION EXISTS DSW 240.12A |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |
| |
| 010 |
( 29) |
OUTLET BOXES ARE NOT COVERED ELECTRIC RM TROUGH COVER MISSINGS TOP OF SERVICE |
RSLV |
07/05/2012 |
07/05/2012 |
08/01/2012 |