| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
1 - 1200AMP SWITCH |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
1 SET 600 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: GRD ELECTRODE COND NOT PROVIDED FOR TRANS... - 250.30 |
RSLV |
05/23/2012 |
05/23/2012 |
08/16/2012 |
| |
| 002 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BSMT INSTALLATION OF 1200AMP.DISC.SW.TAP OFF LOADSIDE EXTING 400AMPSERV.SW PROVIDED CAL# |
OPEN |
08/16/2012 |
08/16/2012 |
|
| |
| 003 |
(999) |
OTHER ROOF BSMT ALL HIGH VOLTAGE DISCONNECT SWS NO WARNING LABEL NOT PRO-VIDED SECTION 408.3 AMENDMENT |
OPEN |
08/16/2012 |
08/16/2012 |
|
| |
| 004 |
(999) |
OTHER A)BSMT NEW 400 KVA TRANSORMER PRIMARY 208 (X)SECONDARY 4801277(H) |
OPEN |
08/16/2012 |
08/16/2012 |
|
| |
| 005 |
(999) |
OTHER B)BSMT ART 110.26 FIRE RATED DOOR WITH PANIC HARD WARE NOT PROVIDEDFOR NEVV 1200AM DISC.SW TAP OFF LOADSIDE EXISTING 9000AMP SERV SW |
OPEN |
08/16/2012 |
08/16/2012 |
|
| |
| 006 |
(999) |
OTHER C)ROOF BSMT VERTICAL CONDUCTORS SUPPORT SPACING IS NOT AS PER ART 300.19 |
OPEN |
08/16/2012 |
08/16/2012 |
|
| |
| 007 |
(999) |
OTHER ROOF CHILLER NOT LISTED AS PER ART 110.2 |
OPEN |
08/16/2012 |
08/16/2012 |
|
| |
| 008 |
(999) |
OTHER D)ROOF CHILLER NOT LISTED AS PER ART 110.2 |
OPEN |
08/16/2012 |
08/16/2012 |
|
| |
| 009 |
(999) |
OTHER E)BSMT JUNCTING BOXES NOT ACCESSIBLE ART 314.29 (BSMT TO ROOF) |
OPEN |
08/16/2012 |
08/16/2012 |
|