Electrical Application Details for App #: Z127738
Premises: 2681 BROADWAY MANHATTAN BIN: 1056558     Block: 1874   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 235 W 102ND ST Census Tract:   1910 Health Area:  3110
BOARDWAY Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   BROADWAY,    WEST END AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/29/2010 11:55 AM
Application Entered:   09/29/2010 Job Start Date:   01/17/2011
Last Change:   08/22/2025 Job End Date:   12/31/2011
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     02/27/2013      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010118 Licensee Name: ROBERT MARCHISOTTO
Firm: 002914 Firm Name: R.C.M. ELECTRIC CORP.
Firm Phone: 718-339-2680  Firm Address: 1915 MCDONALD AVE. BLDG REAR BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $540.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   CONDOMINIUM
Special Cert Approval:   L - FIRE ALARM LOCAL LAW #5
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JIM COTTER
Owner Business Name: MARK GREEBERG REAL ESTATE
Authorized Representative:  JIM COTTER
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 01/24/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z127738
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/31/2012 01/10/2013 DNM N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCEL
 
(2) 01/15/2013 01/24/2013 ARW A (120) (6) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(3) 02/27/2013 03/11/2013 TSO J Y (30) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 04/03/2013 04/17/2013 EDB Z (0) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z127738
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
CELLAR: BREAKER SPACE OPEN IN CAB LIGHT PANEL
RSLV 01/15/2013 01/15/2013 02/27/2013
 
002 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
CELLAR: ALL 4 CONTROLLERS HAVE 2 GROUNDS UNDER SAME LUG
RSLV 01/15/2013 01/15/2013 02/27/2013
 
003 (315) CONDUCTORS NOT PROPERLY IDENTIFIED
CELLAR: WIRES IN DISCONNECTS 1,3 HAVE WIRE IDENTIFIED SMALLER THAN#4
OPEN 01/15/2013 02/27/2013
 
004 (300) ELEVATOR DISCONNECT IS NOT LOCKABLE TYPE
CELLAR: NO LOCKABLE DISCONNECT FOR CAB LIGHTS CARS 1,2 AND 3
RSLV 01/15/2013 01/15/2013 02/27/2013
 
005 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
CELLAR: GROUND CONDUCTOR IN DISCONNECTS 1 AND 2 NOT GREEN
OPEN 01/15/2013 02/27/2013
 
006 (999) OTHER
CELLAR: ALL 4 MOTORS NOT LISTED...... - 110.3
RSLV 01/15/2013 01/15/2013 02/27/2013