| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
4 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX CELLAR: BREAKER SPACE OPEN IN CAB LIGHT PANEL |
RSLV |
01/15/2013 |
01/15/2013 |
02/27/2013 |
| |
| 002 |
(308) |
CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED CELLAR: ALL 4 CONTROLLERS HAVE 2 GROUNDS UNDER SAME LUG |
RSLV |
01/15/2013 |
01/15/2013 |
02/27/2013 |
| |
| 003 |
(315) |
CONDUCTORS NOT PROPERLY IDENTIFIED CELLAR: WIRES IN DISCONNECTS 1,3 HAVE WIRE IDENTIFIED SMALLER THAN#4 |
OPEN |
01/15/2013 |
02/27/2013 |
|
| |
| 004 |
(300) |
ELEVATOR DISCONNECT IS NOT LOCKABLE TYPE CELLAR: NO LOCKABLE DISCONNECT FOR CAB LIGHTS CARS 1,2 AND 3 |
RSLV |
01/15/2013 |
01/15/2013 |
02/27/2013 |
| |
| 005 |
(272) |
EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED CELLAR: GROUND CONDUCTOR IN DISCONNECTS 1 AND 2 NOT GREEN |
OPEN |
01/15/2013 |
02/27/2013 |
|
| |
| 006 |
(999) |
OTHER CELLAR: ALL 4 MOTORS NOT LISTED...... - 110.3 |
RSLV |
01/15/2013 |
01/15/2013 |
02/27/2013 |