BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z127492
Premises: 33 WEST END AVENUE MANHATTAN BIN: 1087589     Block: 1171   Lot: 7506
   
Application Completed and Certified

Filed: 33 W END AV Census Tract:   1510 Health Area:  3900
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
Special Place Name:   SER.ROOM
DOB Cross Street(s):   WEST 61 STREET,    WEST 61 DRIVE
Status:   C - JOB IS SIGNED OFF 10/12/2011
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   03/14/2011 Job Start Date:   03/14/2011
Last Change:   10/12/2011 Job End Date:   12/31/2011
Appointment Status:   
Last Inspection By:   BEST, J       On     09/20/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011918 Licensee Name: LUKASZ TYKA
Firm: 003946 Firm Name: CENTRUM ELECTRIC CORP
Firm Phone: 917-543-9736  Firm Address: 12 LOMBARDY STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $220.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   5052811A0044
Owner / Occup:
Owner Business Name: ATLANTIC DEVELOPMENT LLC
Authorized Representative:  DARIUSZ SKALSKI
Relationship To Owner:   MEMBER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  09/08/2010
Power Issued: Response: F - FILED TO REMOVE OBJECTION 03/14/2011

Follow-Up: X - FILED APPL,NOW CLOSED 03/14/2011
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z127492
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/10/2010 09/08/2010 NEI W (1) (2)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 09/20/2011 09/27/2011 JSB C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z127492
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
NO PANIC BARS IN SER ROOM........110.26.C2
RSLV 07/10/2010 07/10/2010 09/20/2011
 
002 (999) OTHER
STORAGE IN SER ROOM...........110.6.B*RE: Z124060*
RSLV 07/10/2010 07/10/2010 09/20/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back