Electrical Application Details for App #: Z127485
Premises: 602 WEST 112 STREET MANHATTAN BIN: 1057331     Block: 1894   Lot: 56
   
Application Completed and Certified

Filed: 610 W 112 ST Census Tract:   1990 Health Area:  2310
9TH FL.SCHOOL Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   109
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 08/18/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/07/2010 8:52 PM
Application Entered:   09/07/2010 Job Start Date:   09/11/2010
Last Change:   08/18/2011 Job End Date:   09/11/2010
Appointment Status:   
Last Inspection By:   BEST, J       On     07/19/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011169 Licensee Name: LAWRENCE WALSH
Firm: 002541 Firm Name: BDS ELECTRIC CORP.
Firm Phone: 718-598-0000  Firm Address: 220-04 HEMPSTEAD AVENUE QUEENS VILLAGE NY 11429 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $115.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FRANK GARCIA
Authorized Representative:  FRANK GARCIA
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3#6S
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1 200A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
MZ9  9FL  13  20    13             
Buildings Total 13  20    13                
Total Units : 50 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/10/2011
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FIRE ALARM 13 FIXTURES 4 SWITHES, 20 OUTLETS, 1 200A PANEL AC FEEDER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z127485
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/04/2011 03/10/2011 CCH V (60) (7) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 07/19/2011 07/28/2011 JSB C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z127485
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
OFFICE: OUTLET NOT BONDED - NO GREEN WIRE...... - 250.146
RSLV 03/04/2011 03/04/2011 07/19/2011
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
ELE ROOM: KO MISSING PULLBOX NEXT TO PANEL AND CEILING
RSLV 03/04/2011 03/04/2011 07/19/2011
 
003 (999) OTHER
PANEL: DOUBLE LUG UNDER SCREW IN PANEL..... - 408.21
RSLV 03/04/2011 03/04/2011 07/19/2011
 
004 (999) OTHER
PANEL: NEUTRAL BONDED IN PANEL....... - 250.24.A.5
RSLV 03/04/2011 03/04/2011 07/19/2011
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PANEL: NO PANEL DIR
RSLV 03/04/2011 03/04/2011 07/19/2011
 
006 ( 29) OUTLET BOXES ARE NOT COVERED
A) CEILING: AIR HANDLE IN CEILING NEED SWITCH COVER
RSLV 03/04/2011 03/04/2011 07/19/2011
 
007 ( 29) OUTLET BOXES ARE NOT COVERED
B) CEILING: SPLICE BOX - NO COVER IN CEILING
RSLV 03/04/2011 03/04/2011 07/19/2011