BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z125307
Premises: 314 WEST 95 STREET MANHATTAN BIN: 1034183     Block: 1253   Lot: 38
   
Application Completed and Certified

Filed: 316 W 95 ST Census Tract:   183 Health Area:  3110
E.M.R. Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   WEST END AVENUE,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 01/14/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/29/2010 8:25 AM
Application Entered:   03/29/2010 Job Start Date:   03/29/2010
Last Change:   01/14/2014 Job End Date:   03/29/2011
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     12/16/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010996 Licensee Name: ISAAC GELB
Firm: 003314 Firm Name: CHAIM ELEC. CORPORATION
Firm Phone: 718-677-1040  Firm Address: 2920 AVENUE J BROOKLYN NY 11210 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH PODALSKY
Owner Business Name: 316 PENNINGTON LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/30/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z125307
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/05/2013 03/14/2013 JKF N (30) (0) Y
INSPECTION COMMENTS: *BUILDING MANAGER CALLED ELEVATOR - NO ONE SITE*
 
(2) 03/26/2013 04/04/2013 LBI Z (0) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELLATION
 
(3) 04/22/2013 04/30/2013 MFF A (40) (4) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(4) 11/20/2013 11/26/2013 BMP N (30) (0) Y
INSPECTION COMMENTS: NONE
 
(5) 12/16/2013 01/14/2014 BMP C R (25) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z125307
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
BSMT: ELEVATOR PIT G.F.C.I.IS DEFECTIVE
RSLV 04/22/2013 04/22/2013 12/16/2013
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
ROOF: 100A DISCONNECT MISSING KO
RSLV 04/22/2013 04/22/2013 12/16/2013
 
003 (150) MOTOR OVERCURRENT PROTECTON NOT PROPERLY INSTALLED/SIZED
ROOF: #6 WIRES WITH 100A FUSES
RSLV 04/22/2013 04/22/2013 12/16/2013
 
004 (999) OTHER
ROOF: 100A DISCONNECT GROUND WIRES UNDER THE SAME LUG.. - 110.14(A)
RSLV 04/22/2013 04/22/2013 12/16/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order