BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z124732
Premises: 169 WEST 72 STREET MANHATTAN BIN: 1029916     Block: 1144   Lot: 1
   
Application Completed and Certified

Filed: 175 W 72 ST Census Tract:   157 Health Area:  4000
BSMT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   C - JOB IS SIGNED OFF 01/10/2011
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   05/25/2010 Job Start Date:   05/25/2010
Last Change:   01/10/2011 Job End Date:   12/20/2010
Appointment Status:   
Last Inspection By:   BEST, J       On     07/26/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011538 Licensee Name: NICHOLAS BLASONE
Firm: 003044 Firm Name: NEW CENTURY ELEC'L CONTR
Firm Phone: 718-441-7123  Firm Address: 105-15 JAMAICA AVE INC. QUEENS NY 11418 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $295.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LAUB MICHAEL
Owner Business Name: G&L REALTY DELAWARE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1-600A. S.S.
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  2 SETS # 300MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  02/08/2010
Power Issued: Response: F - FILED TO REMOVE OBJECTION 05/25/2010

Follow-Up: X - FILED APPL,NOW CLOSED 05/25/2010
Contractor's Comments:  REMOVE 2-200A. SWITCHES REPLACE W/ 1-600A SWITCH

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z124732
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/02/2010 02/08/2010 CLC W (15) (3)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 07/26/2010 07/30/2010 JSB C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z124732
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT MORE THAN 6 SERVICE SW PROVIDED.....230.71
RSLV 02/02/2010 02/02/2010 07/26/2010
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BASEMENT SERVICE AREA OPEN BOXES
RSLV 02/02/2010 02/02/2010 07/26/2010
 
003 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
BASEMENT SERVICE AREA*NOT FINAL INSPECTION*
RSLV 02/02/2010 02/02/2010 07/26/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.