BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z124233
Premises: 215 WEST 92 STREET MANHATTAN BIN: 1033612     Block: 1240   Lot: 24
   
Application Completed and Certified

Filed: 215 W 92 ST Census Tract:   179 Health Area:  3120
GROUND FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   AMSTERDAM AVENUE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 06/22/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/14/2009 1:28 PM
Application Entered:   12/14/2009 Job Start Date:   12/15/2009
Last Change:   06/22/2010 Job End Date:   01/15/2010
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     06/17/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009742 Licensee Name: HARVEY GILSTON
Firm: 000590 Firm Name: GILSTON ELEC. MAINT. CORP
Firm Phone: 718-294-4400  Firm Address: 453 EAST 175TH STREET BRONX NY 10457 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $150.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   ICE CREAM SHOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DON WILSON
Owner Business Name: BLUEWOODS MGMT.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
GND    28  26    28  10  10     
Buildings Total 35  34    35     10     10      
Total Units : 131 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/14/2009 Notice: 1 - FIRST NOTICE 04/20/2010
Power Issued: 12/14/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SUPPLY AND INSTALL WIRING FOR NEW STORE - 200 AMP SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z124233
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/14/2010 04/20/2010 CCH A E (30) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 06/17/2010 06/22/2010 DAH C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z124233
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BASEMENT: 200 DIS SW FUSES NOT SAME SIZE
RSLV 04/14/2010 04/14/2010 06/17/2010
 
002 ( 19) DEFECTIVE WIRING IS IN USE
BASEMENT: TAP ON ONE WIRE ONLY,ALSO END OF WIRE EXPOSED
RSLV 04/14/2010 04/14/2010 06/17/2010
 
003 (999) OTHER
BASEMENT: DOUBLE LUG IN PANEL.....408.21
RSLV 04/14/2010 04/14/2010 06/17/2010
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
STORE: OUTLET NOT G.F.C.I.KITCHEN
RSLV 04/14/2010 04/14/2010 06/17/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.