| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
3 |
|
| D. 601 Up to 1200 AMPS |
3 |
4 800 AMPS |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
71 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
4 |
|
| D. Over 250 MCM |
3 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
70 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 53) |
GFCI HAS NOT BEEN PROVIDED APTS 707 607 507 407 307 207 ISLAND GFCI NOT PROIVDED |
RSLV |
04/08/2011 |
04/08/2011 |
04/08/2011 |
| |
| 002 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE BSMT FIRE PUMP SVC ENT RACEWAY NOT BONDED |
RSLV |
04/08/2011 |
04/08/2011 |
04/08/2011 |
| |
| 003 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH BSMT 2-400AMP 1-200 1-100 1-60 DISCONN NEUTRAL BAR BONDED AFTER SVCSWS |
RSLV |
04/08/2011 |
04/08/2011 |
04/08/2011 |
| |
| 004 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS BSMT GND ROD RACEWAY NOT CONTINUOUS |
RSLV |
04/08/2011 |
04/08/2011 |
04/08/2011 |
| |
| 005 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS BSMT GND ROD RACEWAY NOT CONTINUOUS |
RSLV |
04/08/2011 |
04/08/2011 |
04/08/2011 |
| |
| 006 |
(999) |
OTHER BSMT: SVC ROOM 2-400,1-200,-1-100/60 AMP DISCONN NEUTRAL BAR BONDEDAND METERS........ - 250.24A5 |
RSLV |
04/08/2011 |
04/08/2011 |
05/07/2011 |
| |
| 007 |
(999) |
OTHER BSMT: FIRE PUMP SVC SW ENT NOT BONDED |
RSLV |
04/08/2011 |
04/08/2011 |
05/07/2011 |
| |
| 008 |
(999) |
OTHER APTS: 707,607,,507,407,,307,207 ISLANDS G.F.C.I.NOT PROVIDED210.8 |
RSLV |
04/08/2011 |
04/08/2011 |
05/07/2011 |