BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z123928
Premises: 125 WEST 82 STREET MANHATTAN BIN: 1070806     Block: 1213   Lot: 7503
   
Application Completed and Certified

Filed: 127 W 82 ST Census Tract:   169 Health Area:  3500
APT.5D Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   C - JOB IS SIGNED OFF 10/20/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/15/2009 2:40 PM
Application Entered:   11/15/2009 Job Start Date:   11/15/2009
Last Change:   10/20/2010 Job End Date:   12/30/2009
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     09/17/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010939 Licensee Name: MICHAEL L ALPHONSE
Firm: 002249 Firm Name: BESTCO GENERAL ELEC. MAIN
Firm Phone: 718-324-5582  Firm Address: 922 EAST 233RD STREET BRONX NY 10466 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DOROTHY SUECOFF
Authorized Representative:  DOROTHY SUECOFF
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
MZ4                     
Buildings Total                     
Total Units : 12 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/01/2010
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACE 4-LIGHT SWITCHES AND 8-LIGHT FIXTURES

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z123928
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/28/2010 02/02/2010 DAH N (30) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 03/29/2010 04/01/2010 CCH A (45) (3) Y
INSPECTION COMMENTS: NO SHOW - NOT FINAL SEE VIOLATION DETAILS
 
(3) 09/17/2010 09/24/2010 CLC C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z123928
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
KITCHEN: CEILING LIGHT FIXTURE CHAIN BROKEN
RSLV 03/29/2010 03/29/2010 09/17/2010
 
002 (999) OTHER
KITCHEN: LIGHTING ON C.T.CIRCUIT.....210.52.B.2
RSLV 03/29/2010 03/29/2010 09/17/2010
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
KITCHEN: OUTLET NOT G.F.C.I..C.T
RSLV 03/29/2010 03/29/2010 09/17/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order