Electrical Application Details for App #: Z123389
Premises: 37 WEST 97 STREET MANHATTAN BIN: 1074358     Block: 1833   Lot: 7501
   
Application Completed and Certified

Filed: 382 CENTRAL PARK W Census Tract:   185 Health Area:  3210
15TH FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
Special Place Name:   JOSE APT.15D
DOB Cross Street(s):    97 ST TRANSVERSE,    COLUMBUS AVENUE
Status:   C - JOB IS SIGNED OFF 03/05/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/30/2009 6:12 PM
Application Entered:   09/30/2009 Job Start Date:   10/02/2009
Last Change:   03/05/2015 Job End Date:   12/31/2009
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     08/01/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010297 Licensee Name: FERDINAND G MASSIMO
Firm: 003749 Firm Name: ELECTRICAL DESIGN MNGT LL
Firm Phone: 212-245-2433  Firm Address: 939 8TH AVENUE SUITE 301 LLC NEW YORK NY 10019 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $71.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSE M JIMENEZ
Owner Business Name: OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
015          15     
Buildings Total           15      
Total Units : 42 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 12/29/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOSE M JIMENEZ - ALTERATIONS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z123389
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/03/2011 02/03/2011 CLC Z (0) (0) Y
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 04/04/2011 04/07/2011 JSB A (60) (2) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(3) 10/31/2011 11/07/2011 CLC Z (0) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELED APPOINTMENT WITH OFFICE
 
(4) 03/09/2012 03/19/2012 CLC A R (30) (1) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(5) 12/13/2012 12/29/2012 TSO A X (20) (9) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(6) 02/21/2013 03/04/2013 LBI N (30) (0) Y
INSPECTION COMMENTS: *TENANT HAD EMERGENCY - NO ACCESS TO APT.15D*
 
(7) 07/15/2013 07/24/2013 JVA J Y (50) (0) Y
INSPECTION COMMENTS: NONE
 
(8) 08/01/2013 03/05/2015 BMP C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z123389
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
KITCHEN: UNDER COUNTER OUTLETS PLUG
RSLV 04/04/2011 04/04/2011 03/09/2012
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
KITCHEN: UNDER COUNTER OUTLETS PLUGMOLD
RSLV 04/04/2011 04/04/2011 03/09/2012
 
003 (999) OTHER
APT.15D: KITCHEN COUNTER AND PENINSULAR NOT G.F.C.I.PROTECTED.... -210.52
RSLV 03/09/2012 07/15/2013 08/01/2013
 
004 ( 30) OUTLET BOXES ARE NOT SECURED
KITCHEN: BOX FOR G.F.C.I.NOT SECURE
RSLV 12/13/2012 07/15/2013 08/01/2013
 
005 ( 19) DEFECTIVE WIRING IS IN USE
KITCHEN: WIRE MOLD NOT ASSEMBLED CONTINUOUS
RSLV 12/13/2012 07/15/2013 08/01/2013
 
006 ( 19) DEFECTIVE WIRING IS IN USE
KITCHEN: WHITE WIRE USED AS GROUND
RSLV 12/13/2012 07/15/2013 08/01/2013
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
KITCHEN: OUTLET BOX NOT GROUNDED
RSLV 12/13/2012 07/15/2013 08/01/2013
 
008 ( 19) DEFECTIVE WIRING IS IN USE
KITCHEN: BARE CONDUCTORS RUN TO ISLAND G.F.C.I
RSLV 12/13/2012 07/15/2013 08/01/2013
 
009 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
KITCHEN: KO MISSING T-11 BOX KITCHEN COUNTER
RSLV 12/13/2012 07/15/2013 08/01/2013
 
010 (999) OTHER
KITCHEN: NOT REQUIRED RECEPTACLES COUNTER...... - 210.52
RSLV 12/13/2012 07/15/2013 08/01/2013
 
011 (999) OTHER
KITCHEN: G.F.C.I.NOT T/R RATED...... - 406.11
RSLV 12/13/2012 12/13/2012 07/15/2013
 
012 ( 29) OUTLET BOXES ARE NOT COVERED
KITCHEN: MISSING COVER PLATE UNDER COUNTER
RSLV 12/13/2012 07/15/2013 08/01/2013