BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z121602
Premises: 137 WEST 74 STREET MANHATTAN BIN: 1030058     Block: 1146   Lot: 14
   
Application Completed and Certified

Filed: 137 W 74 ST Census Tract:   161 Health Area:  3500
HOUSE Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
Related Job Number:    110103735
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   C - JOB IS SIGNED OFF 11/22/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/08/2009 12:59 PM
Application Entered:   05/08/2009 Job Start Date:   05/11/2009
Last Change:   11/22/2010 Job End Date:   12/30/2009
Appointment Status:   
Last Inspection By:   BANYA, E       On     11/10/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
Total Fee:  $527.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 137W 74ST LLC
Authorized Representative:  MR HAMMERSCHLAG
Relationship To Owner:   X


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMPS 3 PHASE
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  2 SETS OF 4#2 MCM
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 SET OF 4#3/0 MCM
D. Over 250 MCM  1  SET OF 4 # 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL  CELL  65  32    65         
BAS  BAS  35  15    35         
001  1ST  64  32    64         
002  2ND  69  34    69         
003  3ND  67  37    67         
004  4TH  59  32    59  10         
Buildings Total 359  182    20  359     20           
Total Units : 940 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/08/2009 Notice: 1 - FIRST NOTICE 04/19/2010
Power Issued: 05/08/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z121602
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/12/2010 04/19/2010 CCH V G (45) (3) Y
INSPECTION COMMENTS: *JOB NOT COMPLETED - CONTRACTOR REFILED FOR SERVICE ONLY* SEE VIOLATION DETAILS
 
(2) 09/13/2010 09/15/2010 WMK Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 11/10/2010 11/17/2010 EBA C R E (30) (0) Y
INSPECTION COMMENTS: *CONTRACTOR ONLY DID SERVICE - SEE DETAILS*

OBJECTION FOR APPLICATION #: Z121602
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BASEMENT: WATER GROUND CABLE NOT CONNECTED
RSLV 04/12/2010 04/12/2010 11/10/2010
 
002 (999) OTHER
A) BSMT: SUPP.GROUND RAVEWAY NOT CONTINUOUS.....250.64.E
RSLV 04/12/2010 04/12/2010 11/10/2010
 
003 (999) OTHER
B) BSMT: LINE AND LOAD SAME RACEWAY......230.7
RSLV 04/12/2010 04/12/2010 11/10/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back