BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z121389
Premises: 400 WEST 63 STREET MANHATTAN BIN: 1088271     Block: 1171   Lot: 145
   

Filed: 400 W. 63RD ST Census Tract:   151 Health Area:  3900
GROUND Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10069 Community Board:   107
Special Place Name:   RIVERSIDE SOUTH J2
Related Job Number:    104872014
DOB Cross Street(s):   FREEDOM PLACE SOUTH,    RIVERSIDE BOULEVARD
Status:   K - CLOSED/CANCELLED 09/19/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/17/2009 12:13 PM
Application Entered:   04/17/2009 Job Start Date:   04/23/2009
Last Change:   09/19/2011 Job End Date:   04/23/2010
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     09/12/2011      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  

License #: 011027 Licensee Name: GARY SEGAL
Firm: 000526 Firm Name: FIVE STAR ELECTRIC CORP.
Firm Phone: 718-641-5000  Firm Address: 101-32 101ST STREET OZONE PARK NY 11416 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $57.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH MONTANO
Owner Business Name: EXTELL DEVELOPMENT CORP.
Authorized Representative:  JOSEPH MONTANO
Relationship To Owner:   VICE PRESIDENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    40        40             
Buildings Total 40        40                
Total Units : 80 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB #2557

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z121389
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/12/2011 09/19/2011 CLC K (15) (0) Y
INSPECTION COMMENTS: SHED REMOVED




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back