BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z120738
Premises: 241 WEST 97 STREET MANHATTAN BIN: 1086955     Block: 1869   Lot: 7503
   
Application Completed and Certified

Filed: 241 W 97 ST Census Tract:   183 Health Area:  3110
PHA Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
Special Place Name:   ROBIN JANIS
DOB Cross Street(s):   BROADWAY,    WEST END AVENUE
Status:   C - JOB IS SIGNED OFF 09/20/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/18/2009 9:24 PM
Application Entered:   02/18/2009 Job Start Date:   02/25/2009
Last Change:   09/20/2010 Job End Date:   05/29/2009
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     09/13/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011958 Licensee Name: SUK Y KIM
Firm: 002493 Firm Name: ASKO ELEC CONST & MAIN IN
Firm Phone: 718-786-8833  Firm Address: 21-24 39TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $77.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBIN JANIS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
PEN  PHA  10    14             
Buildings Total 10    14                
Total Units : 40 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/01/2010
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z120738
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/24/2010 06/01/2010 EBA A (45) (2) Y
INSPECTION COMMENTS: NONE
 
(2) 09/13/2010 09/20/2010 CLC C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z120738
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
BEDROOM,NO ARC FAULT BREAKER PROVIDED FOR RECEPTACLES & LIGHTS
RSLV 05/24/2010 05/24/2010 09/13/2010
 
002 (999) OTHER
BATHROOM FIXTURE ABOVE SHOW IS NOT WATER PROOF 410.4
RSLV 05/24/2010 05/24/2010 09/13/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back