Electrical Application Details for App #: Z115120
Premises: 611 WEST 137 STREET MANHATTAN BIN: 1062264     Block: 2086   Lot: 11
   
Application Completed and Certified

Filed: 611 W 137 ST Census Tract:   223.01 Health Area:  0900
16,26,36,46,34,25,43,31 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10031 Community Board:   109
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 11/24/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/03/2007 3:47 PM
Application Entered:   12/03/2007 Job Start Date:   12/03/2007
Last Change:   11/24/2009 Job End Date:   01/30/2008
Appointment Status:   
Last Inspection By:   RIVERA, F       On     11/16/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011043 Licensee Name: KEVIN J BREEN
Firm: 002992 Firm Name: BREEN ELEC'L CONTR'S INC
Firm Phone: 718-499-7363  Firm Address: 128 EAST BROADWAY NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $242.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: EXTELL DEVELOPMENT CO.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  10  10 - 100AMP PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 32  80  32  36  40                
Total Units : 220 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/29/2009
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW BX RISERS,PANELS AND BRANCH CIRCUIT WIRING IN APTS. 16, 26, 36, 46, 34, 25, 43, 31 NEW BX RISERS AND PANELS ONLY IN APTS 53 AND 63

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z115120
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/21/2009 09/29/2009 CLC A (90) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 11/16/2009 11/16/2009 FRI C R (60) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z115120
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
APTS,ALL BEDROOM A/C NOT AFCI 46,43,36,34,26,6
RSLV 09/21/2009 09/21/2009 11/16/2009
 
002 ( 19) DEFECTIVE WIRING IS IN USE
APTS,43 KITCHEN COUNTER GFCI MIDDLE
RSLV 09/21/2009 09/21/2009 11/16/2009
 
003 ( 30) OUTLET BOXES ARE NOT SECURED
APT. 34 KITCHEN COUNTER GFCI
RSLV 09/21/2009 09/21/2009 11/16/2009
 
004 ( 19) DEFECTIVE WIRING IS IN USE
APT. 26 KITCHEN COUNTER GFCI OPEN GND
RSLV 09/21/2009 09/21/2009 11/16/2009
 
005 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
APT. 6 KITCHEN COUNTER GFCI
RSLV 09/21/2009 09/21/2009 11/16/2009