Electrical Application Details for App #: Z115057
Premises: 2448 BROADWAY MANHATTAN BIN: 1033560     Block: 1238   Lot: 46
   
Application Completed and Certified

Filed: 212 W 91 ST Census Tract:   179 Health Area:  3120
1TILL15 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   AMSTERDAM AVENUE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 03/19/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/27/2007 9:43 PM
Application Entered:   11/27/2007 Job Start Date:   11/29/2007
Last Change:   03/19/2013 Job End Date:   02/29/2008
Appointment Status:   
Last Inspection By:   BEST, J       On     11/27/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010938 Licensee Name: MEIR MAMAN
Firm: 002248 Firm Name: MEIR ELECTRIC CO.
Firm Phone: 212-734-0962  Firm Address: 423 EAST 78TH STREET NEW YORK NY 10075 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $10,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (5  Stores, 365 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:        Submittal #:   
Owner / Occup:
Owner Business Name: BRCE CAPITAL
Authorized Representative:  HILEL KATS
Relationship To Owner:   MANGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  3000AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  365  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  365  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 365 #4-Wire 4 #10-Wire 2
Existing Meters 5 + New Meters 371 - Removed Meters 4 = Total Meters 372

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/27/2007 Notice: 1 - FIRST NOTICE 10/23/2012
Power Issued: 11/27/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z115057
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/02/2012 08/18/2012 WMK A B (180) (7) Y
INSPECTION COMMENTS: NONE
 
(2) 10/10/2012 10/23/2012 JSB A R E (120) (4) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(3) 11/27/2012 12/04/2012 JSB C R E (60) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 11/27/2012 03/19/2013 JSB C E (60) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z115057
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SVC RM SVC ENDLINE BOX & SVC SWITCHES
RSLV 08/02/2012 08/02/2012 10/10/2012
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
SVC RM SPLICE BOX ABOVE METER BANKS AND SVC END BOX
RSLV 08/02/2012 08/02/2012 10/10/2012
 
003 ( 99) OTHER - OLD CODE
A)SVC RM, WITHSTAND RATING OF DEVICES INSTALLED IN 100AMP AND 200AMP SVC SW IMPROPER RATING ART 110.9,ART 110.10
RSLV 08/02/2012 08/02/2012 10/10/2012
 
004 (999) OTHER
SVC RM GREENFIELD INSTALLED BETWEEN CEILING SPLICE BOXES NO EQUIP GNDING ART 250,118(5)
RSLV 08/02/2012 08/02/2012 10/10/2012
 
005 (999) OTHER
SVC RM MORE THAN THREE CURRENT CARRYING FEEDERS CONDUCTORS INSIDE RACEWAY NOT DERATED ART 310.15 (B)(2) (A)
RSLV 08/02/2012 08/02/2012 10/10/2012
 
006 (999) OTHER
SVC RM,BUILDING STEEL WAS NOT USED AS SUPPLEMENTAL ART 250.52
RSLV 08/02/2012 08/02/2012 10/10/2012
 
007 (999) OTHER
SVC RM,SVC ENT PHASE AND NEUT CONDUCTORS NOT INSTALL IN SAME RACEWAY ART.300.3(B)
RSLV 08/02/2012 08/02/2012 10/10/2012
 
008 (999) OTHER
BSMT: 3000 AMP SVC SW SVC ENT RACEWAY NOT BONDED.... - 250.92
RSLV 10/10/2012 10/10/2012 11/27/2012
 
009 (999) OTHER
BSMT: 1600 AMP SVC SW SVC ENT RACEWAY NOT BONDED...... - 250.92
RSLV 10/10/2012 10/10/2012 11/27/2012
 
010 (999) OTHER
BSMT: SVC SUPPLEMENTAL GRD NOT CONNECTED TO BLDG STEEL.... - 250.52
RSLV 10/10/2012 10/10/2012 11/27/2012
 
011 (999) OTHER
BSMT: 1600 SVC SW SVC ENT COND AMPRE RATING LESS THAN RATING OF SVCDISC MEANS...... - NYC AMEND 230.42(A)(2)
RSLV 10/10/2012 10/10/2012 11/27/2012