| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
2 |
3000AMP |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
365 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
365 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED SVC RM SVC ENDLINE BOX & SVC SWITCHES |
RSLV |
08/02/2012 |
08/02/2012 |
10/10/2012 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED SVC RM SPLICE BOX ABOVE METER BANKS AND SVC END BOX |
RSLV |
08/02/2012 |
08/02/2012 |
10/10/2012 |
| |
| 003 |
( 99) |
OTHER - OLD CODE A)SVC RM, WITHSTAND RATING OF DEVICES INSTALLED IN 100AMP AND 200AMP SVC SW IMPROPER RATING ART 110.9,ART 110.10 |
RSLV |
08/02/2012 |
08/02/2012 |
10/10/2012 |
| |
| 004 |
(999) |
OTHER SVC RM GREENFIELD INSTALLED BETWEEN CEILING SPLICE BOXES NO EQUIP GNDING ART 250,118(5) |
RSLV |
08/02/2012 |
08/02/2012 |
10/10/2012 |
| |
| 005 |
(999) |
OTHER SVC RM MORE THAN THREE CURRENT CARRYING FEEDERS CONDUCTORS INSIDE RACEWAY NOT DERATED ART 310.15 (B)(2) (A) |
RSLV |
08/02/2012 |
08/02/2012 |
10/10/2012 |
| |
| 006 |
(999) |
OTHER SVC RM,BUILDING STEEL WAS NOT USED AS SUPPLEMENTAL ART 250.52 |
RSLV |
08/02/2012 |
08/02/2012 |
10/10/2012 |
| |
| 007 |
(999) |
OTHER SVC RM,SVC ENT PHASE AND NEUT CONDUCTORS NOT INSTALL IN SAME RACEWAY ART.300.3(B) |
RSLV |
08/02/2012 |
08/02/2012 |
10/10/2012 |
| |
| 008 |
(999) |
OTHER BSMT: 3000 AMP SVC SW SVC ENT RACEWAY NOT BONDED.... - 250.92 |
RSLV |
10/10/2012 |
10/10/2012 |
11/27/2012 |
| |
| 009 |
(999) |
OTHER BSMT: 1600 AMP SVC SW SVC ENT RACEWAY NOT BONDED...... - 250.92 |
RSLV |
10/10/2012 |
10/10/2012 |
11/27/2012 |
| |
| 010 |
(999) |
OTHER BSMT: SVC SUPPLEMENTAL GRD NOT CONNECTED TO BLDG STEEL.... - 250.52 |
RSLV |
10/10/2012 |
10/10/2012 |
11/27/2012 |
| |
| 011 |
(999) |
OTHER BSMT: 1600 SVC SW SVC ENT COND AMPRE RATING LESS THAN RATING OF SVCDISC MEANS...... - NYC AMEND 230.42(A)(2) |
RSLV |
10/10/2012 |
10/10/2012 |
11/27/2012 |